Plan Review Notes For Permit 22021127 |
Permit Number |
22021127 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-03 07:14:43 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-22021127 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS. FBC RES R403.7 | | | | 2) SHEET M-3: PLEASE SHOW THE RETURN AIR BACK TO THE | | UNIT IN THE HVAC CLOSET. HOW WILL THE RETURN AIR RETURN | | FROM THE BEDROOM? IS THE DOOR AT THE HVAC CLOSET | | LOUVERED? FBC RES M1602.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|