2022-05-16 09:09:26 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. V7 FRC P3108.2.1 THE TUB AND SHOWER ARE NOT VENTED | | TO CODE. ONLY ONE TRAP IS ALLOWED TO CONNECT UPSTREAM | | OF THE VENT CONNECTION. A VENT MUST BE CONNECTED | | BETWEEN THE TWO TRAPS. | | | | 2. V7 FRC P3108.1 - THE BAR SINK CANNOT CONNECT WITHIN | | THE WET VENT. ONLY BATHROOM GROUP FIXTURES ARE ALLOWED | | TO BE INCLUDED IN THE WET VENT SYSTEM. ALL OTHER | | FIXTURES MUST CONNECT DOWNSTREAM OF THE WET VENT | | SYSTEM. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|