Plan Review Notes
Plan Review Notes For Permit 22021046
Permit Number 22021046
Review Stop E
Sequence Number 2
Notes
Date Text
2022-05-05 07:52:39ELECTRIC REVIEW FAILED
 1) PLEASE LOCATE THE METER BANK AND HOUSE DISCONNECT ON
 A SITE PLANS, ONLY A METER IS SHOWN.FBC 107.2
 2) PLEASE DETAIL ALL CONDUCTOR SIZES, OVERCURRENT
 PROTECTION AND WIRING METHODS FOR THE SERVICE AND
 FEEDERS TO APARTMENTS. NEC 215.5
 3) PLEASE DETAIL ELECTRIC LOAD CALCULATION FOR THE
 ENTIRE ELECTRIC SERVICE. NEC 215.5
 4) PLEASE DETAIL SMOKE DETECTORS ON FLOOR PLANS AS
 REQUIRED FBC RE 2020, 7TH EDITION
 5) PLEASE DETAIL ALL COMMON WIRING OUTDOOR,HALLWAYS,
 INCLUDE WIRING METHODS, CONDUCTOR SIZES AND OVERCURRENT
 PROTECTION. FBC 107.2
 6) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PLEASE PROVIDE A BREAKDOWN OF ALL MATERIALS AND
 LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED
 CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C.
 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  