2022-05-05 07:52:39 | ELECTRIC REVIEW FAILED |
| 1) PLEASE LOCATE THE METER BANK AND HOUSE DISCONNECT ON |
| A SITE PLANS, ONLY A METER IS SHOWN.FBC 107.2 |
| 2) PLEASE DETAIL ALL CONDUCTOR SIZES, OVERCURRENT |
| PROTECTION AND WIRING METHODS FOR THE SERVICE AND |
| FEEDERS TO APARTMENTS. NEC 215.5 |
| 3) PLEASE DETAIL ELECTRIC LOAD CALCULATION FOR THE |
| ENTIRE ELECTRIC SERVICE. NEC 215.5 |
| 4) PLEASE DETAIL SMOKE DETECTORS ON FLOOR PLANS AS |
| REQUIRED FBC RE 2020, 7TH EDITION |
| 5) PLEASE DETAIL ALL COMMON WIRING OUTDOOR,HALLWAYS, |
| INCLUDE WIRING METHODS, CONDUCTOR SIZES AND OVERCURRENT |
| PROTECTION. FBC 107.2 |
| 6) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PLEASE PROVIDE A BREAKDOWN OF ALL MATERIALS AND |
| LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED |
| CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C. |
| 109.3 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |
| |