Plan Review Notes
Plan Review Notes For Permit 22021046
Permit Number 22021046
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-03-08 13:41:02THE EXTENT OF RENOVATION FOR THIS OCCUPANCY WOULD MEET
 THE THRESHOLD OF EXTENSIVE MODIFICATIONS PER NFPA 101
 CHAPTER 43:
  
 43.5.2 EXTENSIVE MODIFICATIONS.
 43.5.2.1 THE MODIFICATION OF AN ENTIRE BUILDING OR AN
 ENTIRE
 OCCUPANCY WITHIN A BUILDING SHALL BE CONSIDERED AS A
 RECONSTRUCTION
 AND SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 43.6
 FOR
 THE APPLICABLE OCCUPANCY, UNLESS OTHERWISE SPECIFIED IN
 43.5.2.2.
  
 43.5.2.3 WHERE THE TOTAL AREA OF ALL THE REHABILITATION
 WORK AREAS
 INCLUDED IN A MODIFICATION EXCEEDS 50 PERCENT OF THE
 AREA OF THE
 BUILDING, THE WORK SHALL BE CONSIDERED AS A
 RECONSTRUCTION AND
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 43.6 FOR
 THE APPLICABLE
 OCCUPANCY, UNLESS OTHERWISE SPECIFIED IN 43.5.2.4.
  
 THIS EXTENT OF REHABILITATION (REMODEL) OF THE
 OCCUPANCY WOULD REQUIRE THE PROPERTY TO ADHERE TO
 CONDITIONS OF:
  
 NFPA 101 CHAPTER 30 NEW APARTMENT BUILDINGS
  
 PLEASE PROVIDE DETAILED PLAN FOR MEETING REQUIREMENTS
 UNDER FLORIDA FIRE PREVENTION CODE.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  
2022-02-28 08:42:24PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  