Plan Review Notes For Permit 22021046 |
Permit Number |
22021046 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-17 15:10:22 | APARTMENT RENOVATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE - FBC | | 602.1 | | | | 2) PLEASE SHOW THE BUILDING SQUARE FOOTAGE - NEEDED TO | | DETERMINE THE BUILDING CONSTRUCTION TYPE. FBC 107.2.1 | | | | 3) PLEASE SHOW THE HOURLY FIRE RATING FOR THE CORRIDOR | | WALLS FBC 420 | | | | 4) PLEASE SHOW THE UNIT ENTRY DOOR HOURLY FIRE RATING | | FBC 716 | | | | 5) PLEASE SHOW THAT THE FIRE RATED UNIT ENTRY DOOR | | NEEDS TO BE SELF CLOSING PER FBC 716.5.9 | | | | 6) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG WINDOW | | DOES NOT MEET THE PRESSURES SHOWN ON THE WINDOW | | SCHEDULE. | | | | 7) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | WINDOWS - FRONT PAGE OF THE PRODUCT APPROVAL SHOWS | | APPROVED PER THE 2014 FBC - NEEDS TO BE APPROVED FOR | | THE 2020 FBC | | | | 8) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | WINDOWS NEEDS TO BE REVIEWED AND MARKED APPROVED BY THE | | ARCHITECT OF RECORD FBC 107.3.4 | | | | 9) PRODUCT APPROVAL PROVIDED FOR THE SINGLE HUNG | | WINDOWS REQUIRES SHUTTERS FBC 1609.1.2 - PLEASE PROVIDE | | A SHUTTER PRODUCT APPROVAL - ALL PRODUCT APPROVALS NEED | | TO BE REVIEWED AND MARKED APPROVED BY THE ARCHITECT OF | | RECORD. | | | | 10) PLEASE SHOW THE WINDOW DESIGNATION ON THE FLOOR | | PLAN ACCORDING TO THE WINDOW SCHEDULE. FBC 107.2.1 |
|