2022-04-25 12:56:52PLAN DENIED
 1) REFER TO SECTION M1602 RETURN AIR NUMBER 4
 RETURN AIR SHALL NOT BE TAKEN FROM BATHROOMS.
 2020 FBC RESIDENTIAL CODE.
 2) REFER TO SECTION 107.2.1.3 QUALITY OF PLANS
 PLAN IS BLURRY CAN'T READ DUCT SIZE OR CFM.
 3) IS THE AIR CONDITIONING SYSTEM NEW OR EXISTING
 IF NEW PLEASE PROVIDE A EQUIPMENT SCHEDULE.