2022-03-29 14:16:19 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22021014 2427 PRESIDENTIAL WAY # 404 |
| |
| 2ND REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| 1.NEW COMMENT: PLAN SHEET P301/NOTE 212; IT IS BROUGHT |
| TO OUR ATTENTION BY THE GENERAL MANAGER OF THE CONDO |
| ASSOCIATION THAT THE RELOCATED DRAIN PIPE FOR THE |
| KITCHEN SINK IS A WASTE STACK VENT WHICH RISES |
| VERTICALLY THROUGH THE KITCHEN WALL IN THE GENERAL |
| VICINITY OF THE KITCHEN SINK. PLEASE NOTE THAT WASTE |
| STACK VENTS SHALL NOT BE OFFSET VERTICALLY OR |
| HORIZONTALLY PER FBC PL 913.2 AND AS SUCH SHALL REMAIN |
| IN THE ORIGINAL LOCATION. PER WPB FBC 107.2.1, MAKE |
| CORRECTION TO DRAWING AS NEEDED AND RESUBMIT. |
| |
| 2.REVISED P-801; SANITARY RISER DIAGRAMS ARE |
| INCOMPLETE. FLOOR PENETRATIONS ARE SHOWN; HOWEVER, |
| THERE IS NO DRAINAGE OR VENTING SHOWN. PER WPB FBC |
| 107.2.1, CORRECT AND RESUBMIT. |
| |
| 3.REGARDING THE NEWLY PROVIDED SHOWER |
| THRESHOLD/LINER/WALL DETAIL, PER WPB FBC 107.2.1, |
| PLEASE PROVIDE THE FOLLOWING INFORMATION AS WAS |
| PREVIOUSLY REQUESTED. |
| ***A) DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL |
| 421.5.2 AS FOLLOWS: |
| LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 |
| INCHES ABOVE THE FINISHED THRESHOLD LEVEL |
| LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED |
| BACKING |
| LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT |
| LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD |
| LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| TOWARD THE FIXTURE DRAIN |
| LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET |
| AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT |
| BETWEEN THE LINER AND THE OUTLET |
| FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE |
| LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY |
| SOUND BASE. |
| ***B) LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING |
| WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1, |
| 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR |
| 421.5.2.6.) |
| ***C) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS |
| SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET |
| ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| ABOVE THE DRAIN OF THE SHOWER. |
| ***D) FBC PL 421.4.1 AND 421.5: FLOOR SURFACES SHALL BE |
| CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT |
| AND WATERPROOF MATERIALS |
| ***E) NEW COMMENT: REGARDING THE LINER EXTENDING INTO |
| THE BATHROOM FLOOR, PER WPB FBC 107.2.1, PROVIDE |
| DETAIL/DIRECTION FOR SHEET APPLIED OR TROWEL APPLIED |
| METHODS TO PREVENT WATER FROM MIGRATING BACK TO THE |
| SHOWER DRAIN PIPE FLOOR PENETRATION. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 22021014 2427 PRESIDENTIAL WAY # 404 |
| |