Plan Review Notes
Plan Review Notes For Permit 22021014
Permit Number 22021014
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-03-24 10:25:15FIRE COMMENTS:
 SUBMISSIONS DID NOT ADDRESS PREVIOUS COMMENTS ON THE
 PLAN SET FOR:
 1) PROVIDE DETAIL ON ANY PENETRATIONS INTO A FIRE RATED
 WALL AND HOW THE RATING WILL BE MAINTAINED. NFPA 101,
 8.3.2
 2) PROVIDE INFORMATION ON THE TESTING OF ALL FLOORING
 MATERIALS TO BE INSTALLED AND THE ACOUSTIC UNDERLAYMENT
 FOR FIRE PERFORMANCE INCLUDING THE CRITICAL RADIANT
 FLUX OF THE MATERIALS. NFPA 101, 10.2.7
 3) ALL FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS SHALL
 BE MAINTAINED OPERATIONAL AT ALL TIMES DURING DEMO AND
 CONSTRUCTION AND ANY IMPAIRMENT THAT EXCEEDS 4 HOURS OF
 CONTINUOUS DURATION WILL REQUIRE A FIRE WATCH TO BE
 IMPLEMENTED. NFPA 1, 16.4.4
 4) ALL FIRE ALARM AND/OR FIRE SPRINKLER WORK REQUIRES
 SEPARATE PERMITS AND SHOP DRAWINGS TO BE SUBMITTED,
 REVIEWED AND APPROVED PRIOR TO ANY WORK ON THESE LIFE
 SAFETY SYSTEMS BY QUALIFIED CONTRACTORS.
 CHARLES R. WALKER, SENIOR FIRE INSPECTOR