2022-03-03 11:10:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22021014 2427 PRESIDENTIAL WAY # 404
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PLAN SHEET P301
 ...A) REGARDING NOTES 208, 209 AND 210: PER WPB FBC
 107.2.1, PROVIDE COMPLIANT SANITARY RISER DIAGRAM FOR
 EACH NEW SHOWER INSTALLATION. TO SHOW COMPLIANCE WITH
 FBC PL CHAPTERS 7, 9 AND 10, SHOW FIXTURE DRAINS,
 APPLICABLE BRANCH AND/OR STACK CONNECTIONS, TRAPS AND
 VENTING; INCLUDE SIZES.
 ...B) REGARDING NOTE 206: PER WPB FBC 107.2.1, ADD TO
 NOTE "THE WASTE CONNECTION OF A RESIDENTIAL DISHWASHER
 SHALL CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE
 TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE
 DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR
 THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF
 A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER
 TOPPER FBC PL 409.4."
 ...C) REGARDING NOTE 203: PER WPB FBC 107.2.1, PROVIDE
 CROSS SECTION SHOWER THRESHOLD/LINER/WALL DETAIL AS
 FOLLOWS:
 ......1) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS
 SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 ABOVE THE DRAIN OF THE SHOWER.
 ......2) FBC PL 421.4.1 AND 421.5: FLOOR SURFACES SHALL
 BE CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE,
 NONABSORBENT AND WATERPROOF MATERIALS
 ......3) FBC PL 421.5.2: LINERS SHALL TURN UP ON ALL
 SIDES NOT LESS THAN 2 INCHES ABOVE THE FINISHED
 THRESHOLD LEVEL
 ......4) FBC PL 421.5.2: LINERS SHALL BE RECESSED AND
 FASTENED TO AN APPROVED BACKING
 ......5) FBC PL 421.5.2: LINERS SHALL NOT BE NAILED OR
 PERFORATED AT ANY POINT LESS THAN 1 INCH ABOVE THE
 FINISHED THRESHOLD
 ......6) FBC PL 421.5.2: LINERS SHALL BE PITCHED
 ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL
 (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE
 FIXTURE DRAIN
 ......7) FBC PL 421.5.2: LINERS SHALL BE SECURELY
 FASTENED TO THE WASTE OUTLET AT THE SEEPAGE ENTRANCE,
 MAKING A WATER-TIGHT JOINT BETWEEN THE LINER AND THE
 OUTLET
 ......8) FBC PL 421.5: FLOORS OR RECEPTORS UNDER SHOWER
 COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY, A
 SMOOTH AND STRUCTURALLY SOUND BASE.
 ......9) FBC PL 421.5.2: LINER MATERIAL (SPECIFY LINER
 MATERIAL COMPLYING WITH ONE OF THE FOLLOWING FBC PL
 SECTIONS-421.5.2.1, 421.5.2.2, 421.5.2.3, 421.5.2.4,
 421.5.2.5 OR 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1
 PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE
 REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED.
 ...D) REGARDING NOTE 201: NOTE IS UNCLEAR. ARE TWO NEW
 LAVATORIES REPLACING ONE EXISTING LAVATORY OR TWO
 EXISTING LAVATORIES? PER WPB FBC 107.2.1, CLARIFY. IF
 TWO ARE REPLACING ONE, THEN PER WPB FBC 107.2.1,
 PROVIDE SANITARY RISER DIAGRAM SHOWING THE NEW
 CONFIGURATION AND COMPLIANCE WITH FBC PL SECTIONS 909,
 911.
 ...E) PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC
 PL 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE
 PIPING LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM
 SLOPE OF 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER
 SHALL HAVE A MINIMUM SLOPE OF 1/8 INCH PER FOOT."
  
 2.PLAN SHEET P401:
 ...A) REGARDING NOTE 110: PER WPB FBC 107.2.1, PROVIDE
 THE FOLLOWING NOTES.
 ......1) MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUALS FOR THE HAND-HELD SHOWERS AND THE INDIVIDUAL
 SHOWER VALVES SHALL BE ON SITE FOR INSPECTION.
 ......2) HAND-HELD SHOWERS SHALL CONFORM TO ASME
 A112.18.1/CSA B125.1. HAND-HELD SHOWERS SHALL PROVIDE
 BACKFLOW PROTECTION IN ACCORDANCE WITH ASME
 A112.18.1/CSA B125.1 OR SHALL BE PROTECTED AGAINST
 BACKFLOW BY A DEVICE COMPLYING WITH ASME A112.18.3 PER
 FBC PL 412.2.
 ......3) INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION
 VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND
 TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION
 SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM
 SETTING OF THE VALVE TO 120DEGREES F, WHICH SHALL BE
 FIELD ADJUSTED IN ACCORDANCE WITH THE MANUFACTURE'S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION PER FBC PL
 412.3.
  
 3. PLAN SHEET P801/WATER HEATER SCHEDULE: SCHEDULED
 A.O. SMITH PNLB-50 APPEARS TO HAVE BEEN REPLACED BY
 ENLB 50. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR THE WATER
 HEATER;
 ...A) HIGHLIGHT THE CORRECT MODEL NUMBER
 ...B) PROVIDE NOTE STATING MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUALS FOR THE WATER HEATER
 SHALL BE SHALL BE ON SITE FOR INSPECTION.
  
 4.WATER HEATER SCHEDULE & DETAIL- PROVIDE DETAIL OF
 WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING
 INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE
 IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL
 DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING
 TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL
 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6,
 504.7, 504.7.1 AND 504.7.2. PLEASE NOTE THAT PER FBC PL
 504.7.2, WHERE A PAN DRAIN WAS NOT PREVIOUSLY
 INSTALLED, A PAN DRAIN SHALL NOT BE REQUIRED FOR A
 REPLACEMENT WATER HEATER INSTALLATION. IF THIS IS THE
 CASE, PLEASE INDICATE SUCH ON THE DETAIL.
  
 5.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 6.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL FOR
 ADDED SHOWER FIXTURE DRAINS WITH A NOTE STATING,
 "HORIZONTAL PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH
 FBC PL TABLE 308.5."
  
 7.PER WPB FBC 107.2.1, PROVIDE RATED UL FLOOR
 PENETRATION ASSEMBLY DETAIL FOR THE NEW SHOWER DRAIN
 PENETRATIONS COMPLYING WITH FBC CHAPTER 7.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 22021014 2427 PRESIDENTIAL WAY # 404
  
  
  