Date |
Text |
2022-03-03 11:10:38 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22021014 2427 PRESIDENTIAL WAY # 404 |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| 1. PLAN SHEET P301 |
| ...A) REGARDING NOTES 208, 209 AND 210: PER WPB FBC |
| 107.2.1, PROVIDE COMPLIANT SANITARY RISER DIAGRAM FOR |
| EACH NEW SHOWER INSTALLATION. TO SHOW COMPLIANCE WITH |
| FBC PL CHAPTERS 7, 9 AND 10, SHOW FIXTURE DRAINS, |
| APPLICABLE BRANCH AND/OR STACK CONNECTIONS, TRAPS AND |
| VENTING; INCLUDE SIZES. |
| ...B) REGARDING NOTE 206: PER WPB FBC 107.2.1, ADD TO |
| NOTE "THE WASTE CONNECTION OF A RESIDENTIAL DISHWASHER |
| SHALL CONNECT DIRECTLY TO A WYE BRANCH FITTING ON THE |
| TAILPIECE OF THE KITCHEN SINK, DIRECTLY TO THE |
| DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER, OR |
| THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE OF |
| A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY |
| FASTENED TO THE UNDERSIDE OF THE SINK RIM OR COUNTER |
| TOPPER FBC PL 409.4." |
| ...C) REGARDING NOTE 203: PER WPB FBC 107.2.1, PROVIDE |
| CROSS SECTION SHOWER THRESHOLD/LINER/WALL DETAIL AS |
| FOLLOWS: |
| ......1) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS |
| SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET |
| ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| ABOVE THE DRAIN OF THE SHOWER. |
| ......2) FBC PL 421.4.1 AND 421.5: FLOOR SURFACES SHALL |
| BE CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, |
| NONABSORBENT AND WATERPROOF MATERIALS |
| ......3) FBC PL 421.5.2: LINERS SHALL TURN UP ON ALL |
| SIDES NOT LESS THAN 2 INCHES ABOVE THE FINISHED |
| THRESHOLD LEVEL |
| ......4) FBC PL 421.5.2: LINERS SHALL BE RECESSED AND |
| FASTENED TO AN APPROVED BACKING |
| ......5) FBC PL 421.5.2: LINERS SHALL NOT BE NAILED OR |
| PERFORATED AT ANY POINT LESS THAN 1 INCH ABOVE THE |
| FINISHED THRESHOLD |
| ......6) FBC PL 421.5.2: LINERS SHALL BE PITCHED |
| ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL |
| (2-PERCENT SLOPE) AND SHALL BE SLOPED TOWARD THE |
| FIXTURE DRAIN |
| ......7) FBC PL 421.5.2: LINERS SHALL BE SECURELY |
| FASTENED TO THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, |
| MAKING A WATER-TIGHT JOINT BETWEEN THE LINER AND THE |
| OUTLET |
| ......8) FBC PL 421.5: FLOORS OR RECEPTORS UNDER SHOWER |
| COMPARTMENTS SHALL BE LAID ON, AND SUPPORTED BY, A |
| SMOOTH AND STRUCTURALLY SOUND BASE. |
| ......9) FBC PL 421.5.2: LINER MATERIAL (SPECIFY LINER |
| MATERIAL COMPLYING WITH ONE OF THE FOLLOWING FBC PL |
| SECTIONS-421.5.2.1, 421.5.2.2, 421.5.2.3, 421.5.2.4, |
| 421.5.2.5 OR 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 |
| PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE |
| REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED. |
| ...D) REGARDING NOTE 201: NOTE IS UNCLEAR. ARE TWO NEW |
| LAVATORIES REPLACING ONE EXISTING LAVATORY OR TWO |
| EXISTING LAVATORIES? PER WPB FBC 107.2.1, CLARIFY. IF |
| TWO ARE REPLACING ONE, THEN PER WPB FBC 107.2.1, |
| PROVIDE SANITARY RISER DIAGRAM SHOWING THE NEW |
| CONFIGURATION AND COMPLIANCE WITH FBC PL SECTIONS 909, |
| 911. |
| ...E) PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC |
| PL 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE |
| PIPING LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM |
| SLOPE OF 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER |
| SHALL HAVE A MINIMUM SLOPE OF 1/8 INCH PER FOOT." |
| |
| 2.PLAN SHEET P401: |
| ...A) REGARDING NOTE 110: PER WPB FBC 107.2.1, PROVIDE |
| THE FOLLOWING NOTES. |
| ......1) MANUFACTURER'S SPECIFICATION/INSTALLATION |
| MANUALS FOR THE HAND-HELD SHOWERS AND THE INDIVIDUAL |
| SHOWER VALVES SHALL BE ON SITE FOR INSPECTION. |
| ......2) HAND-HELD SHOWERS SHALL CONFORM TO ASME |
| A112.18.1/CSA B125.1. HAND-HELD SHOWERS SHALL PROVIDE |
| BACKFLOW PROTECTION IN ACCORDANCE WITH ASME |
| A112.18.1/CSA B125.1 OR SHALL BE PROTECTED AGAINST |
| BACKFLOW BY A DEVICE COMPLYING WITH ASME A112.18.3 PER |
| FBC PL 412.2. |
| ......3) INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION |
| VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR |
| COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT |
| CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND |
| TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION |
| SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM |
| SETTING OF THE VALVE TO 120DEGREES F, WHICH SHALL BE |
| FIELD ADJUSTED IN ACCORDANCE WITH THE MANUFACTURE'S |
| INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| UTILIZED FOR COMPLIANCE WITH THIS SECTION PER FBC PL |
| 412.3. |
| |
| 3. PLAN SHEET P801/WATER HEATER SCHEDULE: SCHEDULED |
| A.O. SMITH PNLB-50 APPEARS TO HAVE BEEN REPLACED BY |
| ENLB 50. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUALS FOR THE WATER |
| HEATER; |
| ...A) HIGHLIGHT THE CORRECT MODEL NUMBER |
| ...B) PROVIDE NOTE STATING MANUFACTURER'S |
| SPECIFICATION/INSTALLATION MANUALS FOR THE WATER HEATER |
| SHALL BE SHALL BE ON SITE FOR INSPECTION. |
| |
| 4.WATER HEATER SCHEDULE & DETAIL- PROVIDE DETAIL OF |
| WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING |
| INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE |
| IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL |
| DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING |
| TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING |
| TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL |
| 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6, |
| 504.7, 504.7.1 AND 504.7.2. PLEASE NOTE THAT PER FBC PL |
| 504.7.2, WHERE A PAN DRAIN WAS NOT PREVIOUSLY |
| INSTALLED, A PAN DRAIN SHALL NOT BE REQUIRED FOR A |
| REPLACEMENT WATER HEATER INSTALLATION. IF THIS IS THE |
| CASE, PLEASE INDICATE SUCH ON THE DETAIL. |
| |
| 5.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| SAME. |
| |
| 6.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL FOR |
| ADDED SHOWER FIXTURE DRAINS WITH A NOTE STATING, |
| "HORIZONTAL PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH |
| FBC PL TABLE 308.5." |
| |
| 7.PER WPB FBC 107.2.1, PROVIDE RATED UL FLOOR |
| PENETRATION ASSEMBLY DETAIL FOR THE NEW SHOWER DRAIN |
| PENETRATIONS COMPLYING WITH FBC CHAPTER 7. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| THURSDAYS |
| |
| 22021014 2427 PRESIDENTIAL WAY # 404 |
| |
| |
| |