2022-02-25 14:22:14FIRE COMMENTS:
 PROVIDE DETAIL ON ANY PENETRATIONS INTO A FIRE RATED
 WALL AND HOW THE RATING WILL BE MAINTAINED. NFPA 101,
 8.3.2
 PROVIDE DETAIL ON THE TESTING OF THE FLOORING AND
 ACOUSTIC UNDERLAYMENT FOR FIRE PERFORMANCE. NFPA 101,
 10.2.7
 PROVIDE NOTE ON PROTECTING ALL LIFE SAFETY/FIRE
 PROTECTION SYSTEMS AND MAINTAINING THEM OPERATIONAL AT
 ALL TIMES DURING THE CONSTRUCTION AND HOW TO ADDRESS
 ANY SYSTEM IMPAIRMENTS. NFPA 1, 16.4.4
 PROVIDE A NOTE THAT ANY WORK ON THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEM MUST BE PERFORMED UNDER SEPARATE
 PERMITS AND CONDUCTED ONLY BY THOSE THAT ARE CERTIFIED
 AND QUALIFIED.
  