2022-03-30 10:47:29 | FIRE REVIEW COMMENTS: | | THE NEW DOUBLE DOOR INSTALLATION MAY REQUIRE A FIRE | | RESISTANCE RATING AND SELF-CLOSING DEVICES WITH | | POSITIVE LATCHING. PROVIDE DOCUMENTATION THAT THE NEW | | DOOR ASSEMBLY PROVIDES ADEQUATE PROTECTION IN THE | | OPENING IN THE CMU WALL ON THE FIRST FLOOR BETWEEN THE | | EXISTING WORK AREA AND THE EXISTING WAREHOUSE. NFPA 101 | | 8.3.3 | | ACKNOWLEDGE RECEIPT OF THE LETTER FROM WIGINTON FIRE | | SYSTEMS CONCERNING COVERAGE. | | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | ALARM SYSTEM REQUIRES SEPARATE PERMIT AND SHOP DRAWINGS | | TO BE SUBMITTED AND APPROVED PRIOR TO ANY WORK BEING | | CONDUCTED ON THESE SYSTEMS. | | THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS MUST | | REMAIN ACTIVE DURING ALL PHASES OF DEMOLITION AND | | CONSTRUCTION. | | C.R. WALKER, SENIOR FIRE INSPECTOR | | 561-804-4762 | | [email protected] | | |
|