Plan Review Notes For Permit 22020991 |
Permit Number |
22020991 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-04-06 09:54:08 | 1ST REVIEW FMC | | PERMIT: 22020991 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE UPDATE THE COVER SHEET TO INCLUDE THE ADDED | | MECHANICAL SHEETS. FBC 107.2.1 | | | | 2) THE UNITS BEING REPLACED, ARE THEY LIKE FOR LIKE | | CHANGE OUTS? IF SO PLEASE PROVIDE THE LIKE FOR LIKE | | CHANGE OUT FORMS FOR EACH, IF NOT PLEASE PROVIDE | | EQUIPMENT SIZING CALCULATIONS FOR EACH. FBC 107.2.1 | | | | 3) SHEET M-2: KEYNOTE 3 STATES YOU WILL ABANDON THE | | EXHAUST FANS AND CAP THEM AT THE ROOF. FMC 403.3.1.1 | | AND TABLE 403.3.1.1 TELL US WE SHALL PROVIDE | | VENTILATION PER THE TABLE. PLEASE PROVIDE THE OUTDOOR | | AIR CALCULATIONS FOR THIS WAREHOUSE. FMC TABLE | | 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|