2022-03-02 07:47:45 | THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L. |
| FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING |
| COMMENTS: |
| |
| 1) PROVIDE DOOR AND WALL DETAILS FOR DOORS, ROLL UP |
| DOORS, WALLS BEING ADDED, AND OR FILLED. |
| |
| 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, |
| MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS |
| AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND |
| APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN |
| SECTION 1.14. |
| |
| 2) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL |
| AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE |
| FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE |
| AND COMPLIANCE BY CERTIFIED CONTRACTORS. |
| |
| 3) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE |
| ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND |
| SHOP DRAWINGS BY CERTIFIED CONTRACTORS. |
| |
| 4) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL |
| REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION |
| PERIODS. |
| |
| 5) COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL |
| BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL |
| DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, |
| EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A |
| PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE |
| SAFETY FEATURES AND EQUIPMENT. |
| |
| 6) FOR THE RECORD PLEASE PROVIDE THE EXISTING EXIT |
| SIGNS AND EMERGENCY LIGHTING FOR EVALUATION PER NFPA |
| 101 CHAPTER 7. |
| |
| |
| |