2022-04-12 14:23:25 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| BU1635 BN4338 |
| ASFPM CFM US-21-11935 |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1.PROVIDE A COPY OF THE MOST RECENT BOUNDY LINE SURVEY. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| |
| 3.PROVIDE SMOKE ALARMS. |
| FBC 1104.1SMOKE ALARMS IN EXISTING PORTIONS OF A |
| BUILDING. |
| WHERE AN ADDITION IS MADE TO A BUILDING OR STRUCTURE OF |
| A GROUP R OR I-1 OCCUPANCY, THE EXISTING BUILDING SHALL |
| BE PROVIDED WITH SMOKE ALARMS AS REQUIRED BY THE |
| FLORIDA FIRE PREVENTION CODE OR SECTION R314 OF THE |
| FLORIDA BUILDING CODE, RESIDENTIAL AS APPLICABLE. |
| R314.2.2ALTERATIONS, REPAIRS AND ADDITIONS. |
| WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| |
| 4.DESIGNER SHALL PLACE THE CEILING AND WALL INSULATION |
| R-VALUE ON PLANS. |
| ENERGY SUBMITTAL STATES CEILING R-VALUE IS R-30 AND |
| WALL R-VALUE IS R-5. |
| R402.1.2INSULATION AND FENESTRATION CRITERIA. |
| THE BUILDING THERMAL ENVELOPE SHALL MEET THE |
| REQUIREMENTS OF TABLE R402.1.2, BASED ON THE CLIMATE |
| ZONE SPECIFIED IN CHAPTER 3. |
| |
| 5.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT |
| APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 |
| FBC, FOR THE PROPOSED WINDOWS AND DOORS. |
| FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER |
| CALCULATED DESIGN PRESSURES ON PLAN PAGER S1.1. |
| TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |
| |