Plan Review Notes
Plan Review Notes For Permit 22020719
Permit Number 22020719
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-03-03 13:25:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE NO INDICATIONS OF WHICH COLUMNS/RAILINGS
 WILL BE REPLACED.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE SPECIFIC
 DETAILS WITH A FLOOR PLAN/HORIZONTAL VIEW OF WHICH/WHAT
 COLUMNS/RAILINGS WILL BE REPLACED.
  
  
  
 2) THERE ARE NO INDICATIONS OF RAILING DETAILS, RAILING
 TYPE, HIEGHT, WIDTH, MATERIAL, ETC.
  
 FOR THE OFFICIAL RECORD, PLEASE INDICATE RAILING
 DETAILS.
  
  
 3) THERE ARE NO INDICATIONS OF LIFE SAFETY
 SUPPORT/PROTECTION SHOULD A COLUMN/RAILING BE REMOVED,
 INCLUDING FALLING DEBRIS PROTECTION.
  
 PLEASE PROVIDE SPECIFIC DETAILS OF PROPOSED LIFE SAFETY
 SUPPORT/PROTECTION OR THE REASON WHY IT IS NOT
 REQUIRED.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  