Plan Review Notes For Permit 22020571 |
Permit Number |
22020571 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2022-05-27 14:57:49 | BUILDING REVIEW APPROVED WITH PROVISO (NOTE: PROVIDE | | INFORMATION PRIOR TO INSTALLATION/INSPECTION TO AVOID | | CONFLICTS/DELAYS): | | 1- SHEETS S-102 AND S-201: ARCHITECT TO REVISE TOP | | CHORD DEAD LOAD FOR ROOF TRUSSES. 5 P.S.F. IS TOO LOW | | FOR CONCRETE ROOF TILE. | | 2- SHEET A-201: ARCHITECT TO REVISE THE WALL PRESSURES | | TABLE. ULTIMATE WIND SPEED DESIGN PRESSURES ARE TOO | | LOW. REVISE ULTIMATE AND NOMINAL DESIGN PRESSURES. | | 3- STAIRWAY CONSTRUCTION: PLANS DON'T PROVIDE STAIRWAY | | DIMENSIONS. NEED ALL THE STAIRWAY DIMENSIONS: WIDTH, | | LANDINGS, ETC. | | NOTE: ALSO, NOTE # 3 ON SHEET A-401 IS NO LONGER A CODE | | REQUIREMENT. THE SPECIFIED RISER AND TREAD DIMENSIONS | | DON'T COMPLY WITH THIS STATEMENT EITHER. REVISE AS | | REQUIRED. | | 4- STAIR SECTION 1 ON SHEET A-401. REVISE FIREBLOCKING | | AT TOP OF STAIRS. 2X FIREBLOCKING AS SHOWN ON THIS | | SECTION DOESN'T PROVIDE FIREBLOCKING TO THE SECOND | | FLOOR AT THE TRIANGLE AREA. | | 5- REVISED STRUCTURAL BUCK DETAILS ON SHEET A-202. | | 2"X4" P.T. PLUS BLOCKING DOESN'T PROVIDE FULL SUPPORT | | TO THE DOOR FRAME. | | 6- PROVIDE PRODUCT APPROVALS APPROVED BY ARCHITECT FOR: | | A)GARAGE EXTERIOR SWING DOOR. B)MASTER BEDROOM EXTERIOR | | SWING DOOR. C)ROOF TILE ADHESIVE LISTED IN ROOF TILE | | PRODUCT APPROVAL. D)ROOF TILE HIP & RIDGE METAL SUPPORT | | TO BE USED. | | 7- PROVIDE DRAINAGE CERTIFICATE. |
|