2022-05-27 11:21:01 | NEW SINGLE FAMILY RESIDENCE(R3) SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22020571 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| ***IMPORTANT*** |
| ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER |
| OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT. |
| |
| |
| 1- ENERGY CALCULATIONS SUBMITTED: |
| ORIGINAL COMMENT: |
| A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE |
| CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S |
| ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING STREET ADDRESS OF JOB, OWNER'S NAME, |
| BUILDER'S NAME AND JURISDICTION NUMBER (THIS |
| JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| ONLY THE STREET ADDRESS WAS PROVIDED. |
| |
| C)OK. |
| D)OK. |
| |
| ORIGINAL COMMENT: |
| E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT: |
| 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD |
| LOADS FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY SECOND |
| FLOOR LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS) AND |
| ROOF LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS), |
| INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE |
| R301.5 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B" AND |
| "G". |
| |
| RESPONSE: |
| ROOF TRUSSES INFORMATION ON SHEETS S-102 AND S-201 |
| SPECIFY 5 P.S.F. TOP CHORD DEAD LOAD FOR ROOF TRUSSES. |
| THIS DESIGN LOAD IS TO LOW IF THE ROOF IS GOING TO |
| RECEIVE CONCRETE TILE. REVISE AS REQUIRED. SEC. R301.4 |
| FBC-RESIDENTIAL. |
| |
| ORIGINAL COMMENT: |
| 3-SHEET A-201: REVISE THE WINDOW DESIGN PRESSURES TO |
| MATCH DESIGN PRESSURES SHOWN ON THE WALL PRESSURES |
| (COMPONENT & CLADDING) TABLE ON SAME SHEET. |
| NOTE: REVISE BASED ON WINDOW SIZE AND ZONE. SEC. |
| R301.2.1 FBC-RESIDENTIAL. |
| SEE FOOTNOTE "B" ON TABLE R301.2.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| WALL PRESSURES TABLE WERE REVISED AND ARE INCORRECT. |
| THE ULTIMATE WIND SPEED DESIGN PRESSURES ARE TOO LOW. |
| THEREFORE, THE NOMINAL WIND SPEED PRESSURES ARE |
| INCORRECT ALSO. REVISE AS REQUIRED. |
| |
| 4- OK. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR STAIRWAY |
| CONSTRUCTION: |
| ORIGINAL COMMENT: |
| A)PLANS DON'T PROVIDE STAIRWAY DIMENSIONS. SEC. |
| R311.7.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. ONLY THE STAIR FLIGHT DIMENSIONS WERE |
| GIVEN. NEED ALL THE STAIRWAY DIMENSIONS: WIDTH, |
| LANDINGS, ETC. |
| |
| B) OK. |
| C) OK. |
| |
| ORIGINAL COMMENT: |
| D)SHEET A-401 NEED TO REFERENCE CORRECT CODE SECTIONS |
| ON THE TYPICAL STAIR NOTES AND TYPICAL RAILING NOTES. |
| SEE SEC. R311.7 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| NOTE # 3 IS NO LONGER A CODE REQUIREMENT. ALSO, THE |
| SPECIFIED RISER AND TREAD DIMENSIONS DON'T COMPLY WITH |
| THIS STATEMENT EITHER. REVISE AS REQUIRED. |
| |
| ORIGINAL COMMENT: |
| E)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11 |
| FBC-RESIDENTIAL. NEED FIREBLOCKING AT TOP AND BOTTOM OF |
| THE RUN. |
| NOTE: FIREBLOCKING AND DRAFSTOPPING ARE TWO DIFFERENT |
| THINGS. SEE SEC. R302.11 FBC-RESIDENTIAL AND SEC. |
| R302.12 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| STAIR SECTION 1 ON SHEET A-401. REVISE FIREBLOCKING AT |
| TOP OF STAIRS. 2X FIREBLOCKING AS SHOWN ON THIS SECTION |
| DOESN'T PROVIDE FULL FIREBLOCKING TO THE SECOND FLOOR |
| AT THE TRIANGLE AREA. REVISE AS REQUIRED. |
| |
| 6- OK. |
| 7- OK. |
| 8- OK. |
| |
| ORIGINAL COMMENT: |
| 9- REVISE DETAIL C ON SHEET A-202. STRUCTURAL BUCK |
| NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AS |
| REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. 2"X4" P.T. |
| BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME. |
| REVISE AS REQUIRED. |
| |
| RESPONSE: |
| REVISED DETAIL STILL SHOWS 2X4 BUCK WITH PERPENDICULAR |
| BLOCKING. THIS BLOCKING IS NOT ENOUGH TO PROVIDE FULL |
| SUPPORT TO THE DOOR FRAME. SEE WALL SECTIONS AND |
| TYPICAL BUCK DETAILS FOR SIZE OF BLOCKING OR FURRING |
| STRIPS. REVISE AS REQUIRED. |
| |
| 10- OK. |
| 11- OK. |
| 12- OK. |
| 13- OK. |
| |
| 14-PROVIDE PRODUCT APPROVALS (FAC 61G20-3.001): NOTE: |
| COORDINATE WITH REVISION REQUIRED ON ITEM #3 ABOVE THEN |
| CHECK PRODUCT APPROVALS DESIGN PRESSURES AND RESUBMIT |
| AS REQUIRED. |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)OK. |
| B)GARAGE EXTERIOR SWING DOOR. |
| C)MASTER BEDROOM EXTERIOR SWING DOOR. |
| D)OK. |
| E)OK. |
| F)OK. |
| G)OK. |
| H)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT |
| APPROVAL. |
| I)OK. |
| J)OK. |
| K)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED. |
| |
| NOTE: FLORIDA PRODUCT APPROVALS: NEED TO PROVIDE |
| COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE. |
| THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE CURRENT CODE |
| VERSION AND THE PRODUCT APPROVAL STATUS. CHAPTER 553 |
| F.S. AND FAC 61G20-3.001 |
| |
| 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT |
| ON SHEET A-202 WITH ALL PRODUCT APPROVALS SUBMITTED. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |