2022-04-05 14:46:27 | ROOFING REVIEW |
| |
| 1-PROVIDE PRODUCT APPROVALS (FAC 61G20-3.001): NOTE: |
| COORDINATE WITH REVISION REQUIRED ON ITEM #3 ABOVE THEN |
| CHECK PRODUCT APPROVALS DESIGN PRESSURES AND RESUBMIT |
| AS REQUIRED. |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| R301.2.1 FBC-RESIDENTIAL. |
| B)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT |
| APPROVAL. |
| C)ROOF TILE UNDERLAYMENT. |
| D) ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED. |
| E)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE |
| TILE. |
| |
| 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT |
| ON SHEET A-202 WITH ALL PRODUCT APPROVALS SUBMITTED. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |