2022-02-28 06:49:46 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-22020571 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROJECT NAME LISTED ON THE ENERGY CALCULATIONS IS |
| ALL RESIDENCE. PLEASE BE SPECIFIC TO THE ACTUAL PROJECT |
| AND ADDRESS OF THE PROJECT. FBC 107.2.1 |
| |
| 2) PROJECT NAME LISTED ON THE MECHANICAL EQUIPMENT |
| SIZING CALCULATIONS IS ALL RESIDENCE. PLEASE BE |
| SPECIFIC TO THE ACTUAL PROJECT AND ADDRESS OF THE |
| PROJECT. FBC 107.2.1 |
| |
| 3) THE DUCTWORK SERVING THE MASTER SUITE AREA IS |
| MISSING A MAIN TRUNK LINE. PLEASE SHOW THE TRUNK LINE |
| ALONG WITH THE SIZE OF THIS TRUNK LINE. FBC 107.2.1 |
| |
| 4) PROVIDE THE CFM?S OF THE KITCHEN HOOD EXHAUST. FBC |
| RES M1503.4 |
| |
| 5) PLEASE SHOW THE DRYER EXHAUST DUCT AND TERMINATION |
| LOCATION FOR THE LAUNDRY ROOM ON THE 2ND FLOOR. FBC RES |
| M1502 AND 1503 |
| |
| 6) PLEASE SHOW THE CONDENSATE DRAIN AND TERMINATION |
| LOCATIONS FOR BOTH MECHANICAL SYSTEMS. FBC RES M1411.3 |
| |
| 7) THE DESIGNER OF THE MECHANICAL DRAWING MUST WRITE |
| AND SIGN THEIR NAME ON THE DRAWING. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |