2022-04-05 14:39:22 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22020571 |
| |
| 1- ENERGY CALCULATIONS SUBMITTED: |
| A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE |
| CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S |
| ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING STREET ADDRESS OF JOB, OWNER'S NAME, |
| BUILDER'S NAME AND JURISDICTION NUMBER (THIS |
| JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION. |
| |
| C)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS |
| AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION. |
| |
| D)ROOF MATERIAL SPECIFIED ON PAGE 2 IS INCORRECT. SEE |
| PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD |
| LOADS FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY SECOND |
| FLOOR LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS) AND |
| ROOF LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS), |
| INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE |
| R301.5 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B" AND |
| "G". |
| |
| 3-SHEET A-201: REVISE THE WINDOW DESIGN PRESSURES TO |
| MATCH DESIGN PRESSURES SHOWN ON THE WALL PRESSURES |
| (COMPONENT & CLADDING) TABLE ON SAME SHEET. |
| NOTE: REVISE BASED ON WINDOW SIZE AND ZONE. SEC. |
| R301.2.1 FBC-RESIDENTIAL. |
| SEE FOOTNOTE "B" ON TABLE R301.2.1 FBC-RESIDENTIAL |
| |
| 4- SHEET A-202: PROVIDE DETAILS/SPECIFICATIONS FOR |
| BALCONY FRAMED KNEE WALL. SPECIFY ALL FRAMING MEMBERS |
| AND CONNECTORS. SPECIFY ALL WALL COMPONENTS/FINISHES. |
| FASTENING. SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| 5- PROVIDE COMPLETE INFORMATION FOR STAIRWAY |
| CONSTRUCTION: |
| A)PLANS DON'T PROVIDE STAIRWAY DIMENSIONS. SEC. |
| R311.7.1 FBC-RESIDENTIAL. |
| |
| B)CLEARLY SPECIFY TREAD DIMENSION. SEE SEC. R311.7.5.2 |
| FBC-RESIDENTIAL FOR PROPER WAY OF MEASURING TREAD. |
| |
| C)PROVIDE NOSING INFORMATION. SEC. R311.7.5.3 |
| FBC-RESIDENTIAL. |
| |
| D)SHEET A-401 NEED TO REFERENCE CORRECT CODE SECTIONS |
| ON THE TYPICAL STAIR NOTES AND TYPICAL RAILING NOTES. |
| SEE SEC. R311.7 FBC-RESIDENTIAL. |
| |
| E)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11 |
| FBC-RESIDENTIAL. NEED FIREBLOCKING AT TOP AND BOTTOM OF |
| THE RUN. |
| NOTE: FIREBLOCKING AND DRAFSTOPPING ARE TWO DIFFERENT |
| THINGS. SEE SEC. R302.11 FBC-RESIDENTIAL AND SEC. |
| R302.12 FBC-RESIDENTIAL. |
| |
| 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF ALL NEW HANDRAILS AND GUARDRAILS, |
| INCLUDING BALCONY GUARDRAIL SHOWING COMPLIANCE WITH |
| TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1 |
| FBC-RESIDENTIAL. |
| NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE |
| DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC. |
| R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS |
| THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW |
| PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED |
| BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL |
| TO THIS OFFICE. |
| |
| 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| DRAFSTOPPING IN SECOND FLOOR AREAS AS REQUIRED BY SEC. |
| R302.12 FBC-RESIDENTIAL. |
| |
| 8- SHEET S-101: FOOTING SCHEDULE DOESN'T PROVIDE |
| SPECIFICATIONS FOR FOOTING MF3 SHOWN ON THE FOUNDATION |
| PLAN. PROVIDE INFORMATION. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 9- REVISE DETAIL C ON SHEET A-202. STRUCTURAL BUCK |
| NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AS |
| REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. 2"X4" P.T. |
| BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME. |
| REVISE AS REQUIRED. |
| |
| 10-REVISE ROOF SHEATHING NAILING TYPE, SIZE AND |
| SPACING. NEED TO USE RING SHANK NAILS AND ROOF |
| SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES O.C. IN |
| THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND |
| TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| NOTE: ROOF SHEATHING SPECIFICATIONS ON DETAIL 2/S-301 |
| AND SPECIFICATIONS SHOWN ON THE DIAPHRAGM SCHEDULE ON |
| SAME SHEET DON'T MATCH. REVISE AS REQUIRED AND REVISE |
| ROOF SHEATHING SPECIFICATION SHOWN ON OTHER WALLS |
| SECTIONS ON DIFFERENT SHEETS TO AVOID CONFLICT/DELAYS. |
| |
| 11-SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE |
| BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL. |
| |
| 12- WIND RESISTANCE OF EXTERIOR SOFFITS: DESIGNER OF |
| RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH |
| SEC. R704 FBC-RESIDENTIAL. |
| |
| 13- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| PROTECTION IF REQUIRED. |
| NOTE: WINDOWS LOCATED ON THE STAIRWAY NEED TO COMPLY |
| WITH THE WINDOW FALL PROTECTION SEC. R312.2 |
| FBC-RESIDENTIAL. PROVIDE COMPLETE DETAIL AND |
| SPECIFICATIONS SHOWING COMPLIANCE. |
| |
| 14-PROVIDE PRODUCT APPROVALS (FAC 61G20-3.001): NOTE: |
| COORDINATE WITH REVISION REQUIRED ON ITEM #3 ABOVE THEN |
| CHECK PRODUCT APPROVALS DESIGN PRESSURES AND RESUBMIT |
| AS REQUIRED. |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)ENTRY DOOR WITH SIDELITES AS SHOWN ABOVE. |
| B)GARAGE EXTERIOR SWING DOOR. |
| C)MASTER BEDROOM EXTERIOR SWING DOOR. |
| D)SINGLE HUNG WINDOWS. |
| E)FIXED WINDOWS. |
| F)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| G)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE |
| USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS |
| TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC |
| R301.2.1 FBC-RESIDENTIAL. |
| H)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT |
| APPROVAL. |
| I)ROOF TILE UNDERLAYMENT. |
| J)OVERHEAD GARAGE DOOR THAT MEETS THE SPECIFIED DESIGN |
| PRESSURES. |
| K)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED. |
| L)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE |
| TILE. |
| |
| NOTE: FLORIDA PRODUCT APPROVALS: NEED TO PROVIDE |
| COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE. |
| THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE CURRENT CODE |
| VERSION AND THE PRODUCT APPROVAL STATUS. CHAPTER 553 |
| F.S. AND FAC 61G20-3.001 |
| |
| 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT |
| ON SHEET A-202 WITH ALL PRODUCT APPROVALS SUBMITTED. |
| |
| 16- VALUATION WAS UPDATED TO $695,451.00 AS REQUIRED BY |
| SEC. 109.3 CITY AMENDMENTS. VALUATION TO INCLUDE ALL |
| LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND |
| DESIGN PROFESSIONAL FEES. THE PERMIT FEE BALANCE IS |
| $11,184.88 |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |