Plan Review Notes
Plan Review Notes For Permit 22020571
Permit Number 22020571
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-05 14:39:22NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020571
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING STREET ADDRESS OF JOB, OWNER'S NAME,
 BUILDER'S NAME AND JURISDICTION NUMBER (THIS
 JURISDICTION IS 604700). SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 D)ROOF MATERIAL SPECIFIED ON PAGE 2 IS INCORRECT. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD
 LOADS FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY SECOND
 FLOOR LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS) AND
 ROOF LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS),
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 FBC-RESIDENTIAL. NOTE: SEE FOOTNOTES "B" AND
 "G".
  
 3-SHEET A-201: REVISE THE WINDOW DESIGN PRESSURES TO
 MATCH DESIGN PRESSURES SHOWN ON THE WALL PRESSURES
 (COMPONENT & CLADDING) TABLE ON SAME SHEET.
 NOTE: REVISE BASED ON WINDOW SIZE AND ZONE. SEC.
 R301.2.1 FBC-RESIDENTIAL.
 SEE FOOTNOTE "B" ON TABLE R301.2.1 FBC-RESIDENTIAL
  
 4- SHEET A-202: PROVIDE DETAILS/SPECIFICATIONS FOR
 BALCONY FRAMED KNEE WALL. SPECIFY ALL FRAMING MEMBERS
 AND CONNECTORS. SPECIFY ALL WALL COMPONENTS/FINISHES.
 FASTENING. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 5- PROVIDE COMPLETE INFORMATION FOR STAIRWAY
 CONSTRUCTION:
 A)PLANS DON'T PROVIDE STAIRWAY DIMENSIONS. SEC.
 R311.7.1 FBC-RESIDENTIAL.
  
 B)CLEARLY SPECIFY TREAD DIMENSION. SEE SEC. R311.7.5.2
 FBC-RESIDENTIAL FOR PROPER WAY OF MEASURING TREAD.
  
 C)PROVIDE NOSING INFORMATION. SEC. R311.7.5.3
 FBC-RESIDENTIAL.
  
 D)SHEET A-401 NEED TO REFERENCE CORRECT CODE SECTIONS
 ON THE TYPICAL STAIR NOTES AND TYPICAL RAILING NOTES.
 SEE SEC. R311.7 FBC-RESIDENTIAL.
  
 E)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING IN ALL THE AREAS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL. NEED FIREBLOCKING AT TOP AND BOTTOM OF
 THE RUN.
 NOTE: FIREBLOCKING AND DRAFSTOPPING ARE TWO DIFFERENT
 THINGS. SEE SEC. R302.11 FBC-RESIDENTIAL AND SEC.
 R302.12 FBC-RESIDENTIAL.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL NEW HANDRAILS AND GUARDRAILS,
 INCLUDING BALCONY GUARDRAIL SHOWING COMPLIANCE WITH
 TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE
 DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS
 THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW
 PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN SECOND FLOOR AREAS AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 8- SHEET S-101: FOOTING SCHEDULE DOESN'T PROVIDE
 SPECIFICATIONS FOR FOOTING MF3 SHOWN ON THE FOUNDATION
 PLAN. PROVIDE INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 9- REVISE DETAIL C ON SHEET A-202. STRUCTURAL BUCK
 NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. 2"X4" P.T.
 BUCK DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME.
 REVISE AS REQUIRED.
  
 10-REVISE ROOF SHEATHING NAILING TYPE, SIZE AND
 SPACING. NEED TO USE RING SHANK NAILS AND ROOF
 SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES O.C. IN
 THE FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: ROOF SHEATHING SPECIFICATIONS ON DETAIL 2/S-301
 AND SPECIFICATIONS SHOWN ON THE DIAPHRAGM SCHEDULE ON
 SAME SHEET DON'T MATCH. REVISE AS REQUIRED AND REVISE
 ROOF SHEATHING SPECIFICATION SHOWN ON OTHER WALLS
 SECTIONS ON DIFFERENT SHEETS TO AVOID CONFLICT/DELAYS.
  
 11-SHOW ON PLANS CARBON MONOXIDE ALARMS BY ALL THE
 BEDROOMS AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 12- WIND RESISTANCE OF EXTERIOR SOFFITS: DESIGNER OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
  
 13- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
 NOTE: WINDOWS LOCATED ON THE STAIRWAY NEED TO COMPLY
 WITH THE WINDOW FALL PROTECTION SEC. R312.2
 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS SHOWING COMPLIANCE.
  
 14-PROVIDE PRODUCT APPROVALS (FAC 61G20-3.001): NOTE:
 COORDINATE WITH REVISION REQUIRED ON ITEM #3 ABOVE THEN
 CHECK PRODUCT APPROVALS DESIGN PRESSURES AND RESUBMIT
 AS REQUIRED.
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR WITH SIDELITES AS SHOWN ABOVE.
 B)GARAGE EXTERIOR SWING DOOR.
 C)MASTER BEDROOM EXTERIOR SWING DOOR.
 D)SINGLE HUNG WINDOWS.
 E)FIXED WINDOWS.
 F)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 G)ROOF TILE AND CLEARLY MARK ADHESIVE PADDY SIZE TO BE
 USED AS REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC
 R301.2.1 FBC-RESIDENTIAL.
 H)ROOF TILE ADHESIVE LISTED IN ROOF TILE PRODUCT
 APPROVAL.
 I)ROOF TILE UNDERLAYMENT.
 J)OVERHEAD GARAGE DOOR THAT MEETS THE SPECIFIED DESIGN
 PRESSURES.
 K)ROOF TILE HIP & RIDGE METAL SUPPORT TO BE USED.
 L)BALCONY UNDERLAYMENT SPECIFIED ON PLANS TO RECEIVE
 TILE.
  
 NOTE: FLORIDA PRODUCT APPROVALS: NEED TO PROVIDE
 COMPLETE PRODUCT APPROVAL INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE.
 THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE CURRENT CODE
 VERSION AND THE PRODUCT APPROVAL STATUS. CHAPTER 553
 F.S. AND FAC 61G20-3.001
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT
 ON SHEET A-202 WITH ALL PRODUCT APPROVALS SUBMITTED.
  
 16- VALUATION WAS UPDATED TO $695,451.00 AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES. THE PERMIT FEE BALANCE IS
 $11,184.88
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  