2022-07-26 16:25:51 | ***THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| PERMIT - CITY RIGHTS-OF-WAY (21100162) MUST BE APPROVED |
| PRIOR TO THIS PERMIT BEING APPROVED. THE PLANS INCLUDED |
| WITH THIS ELECTRICAL PERMIT MUST MATCH THE PLANS |
| APPROVED WITH THE AFOREMENTIONED PERMIT. SOME OF THE |
| COMMENTS BELOW ARE INCLUDED ON THE PLACEMENT PERMIT |
| REVIEW AS WELL AS WITH THIS PERMIT.*** |
| |
| 1. PROPOSED UNDERGROUND ELECTRIC CONNECTS TO POLE THAT |
| IS OUTSIDE OF ROW AND RUNS THROUGH PRIVATE PROPERTY, |
| REQUIRES A UTILITY EASEMENT, OWNER?S CONSENT, OR |
| REROUTE THROUGH THE PUBLIC ROW. |
| - CONDUIT IS IN ROW BUT THE POLE/POWER SOURCE IT PULLS |
| FROM APPEARS TO BE OUTSIDE OF THE ROW AND ON PRIVATE |
| PROPERTY, PER THE SURVEY PROVIDED. |
| |
| 2. SHEET 03 ? PLAN VIEW ? ON THE ENLARGED PLAN VIEW, IT |
| SHOWS THE HANDHOLE/BORE DIRECTLY ADJACENT TO THE TREE |
| GRATES ALONG TAMARIND. THESE LANDSCAPED AREAS FEATURE |
| SILVA CELLS AND STRUCTURAL SOIL AROUND THE TREES, THIS |
| REQUIRES AN 8FT. BUFFER FROM THE TRUNK OF THE TREE, IN |
| ORDER TO AVOID ANY IMPACT TO THE ROOT SYSTEM OR |
| STRUCTURAL SUPPORT OF THE LANDSCAPING. |
| |
| 3. PLEASE PROVIDE THE NECESSARY PUBLIC/PRIVATE UTILITY |
| LETTERS GRANTING APPROVAL OF THE BORE PITS, HANDHOLES, |
| AND UNDERGROUND ELECTRICAL FOR THE PROPOSED POLE |
| LOCATION. |
| |
| 4. POLE LOCATION, HEIGHT, AND STEALTH DESIGN MEETS CITY |
| STANDARDS. |
| |
| |
| CHRIS KIMMERLY, AICP |
| URBAN DESIGN PLANNER |
| [email protected] 822-1426 |
| |