2022-03-01 07:52:48 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-22020407 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC RES R402 |
| |
| 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS. FBC RES R403.7 |
| |
| 3) PLEASE SHOW THE ENERGY CALCULATIONS FOR THE GARAGE |
| AS THIS IS NOT TYPICALLY A CONDITIONED SPACE. FBC RES |
| R402.1 |
| |
| 4) IT APPEARS THAT THE DRYER EXHAUST FROM BOTH DRYERS |
| IN THE LAUNDRY AT THE GARAGE ARE RUNNING INTO ONE 4 |
| INCH DUCT ABOVE THE CEILING AND GOING THRU THE ROOF. |
| PLEASE SHOW THAT EACH DRYER IS GOING SEPARATELY TO THE |
| OUTDOORS OR PROVIDE MANUFACTURE?S INSTALLATION |
| INSTRUCTIONS SHOWING THIS METHOD. FBC RES M1502.3 |
| |
| 5) PLEASE PROVIDE A BATH EXHAUST FAN OR SHOW THE |
| WINDOWS MEET FBC RES R303.3 IN THE 2ND STORY SHOWER |
| AREAS. |
| |
| 6) PLEASE SHOW THE CONDENSATE DRAIN AND TERMINATION |
| LOCATION. FBC RES M1411.3 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |