2022-05-10 14:40:32 | PLAN REVIEW BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| BU1635 BN4338 |
| ASFPM CFM US-21-11935 |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: PROVISO ON PLAN PAGE A-100: A SEPERATE PERMIT |
| IS REQUIRED FOR THE PERGOLA. CT |
| |
| 1. PROVIDE A COVER SHEET. INCLUDE BUILDING DATA AND |
| DESIGN CRITERIA. |
| PROVIDE PROJECT DATA/DESIGN PARAMETERS: |
| |
| PROJECT DATA: 1&2 FAMILY DWELLING UNIT |
| OCCUPANCY CLASSIFICATION R3 SFR |
| SCOPE OF WORK |
| |
| DESIGN PARAMETERS: 2020 FBC EXISTING BUILDING |
| 2020 FBC RESIDENTIAL |
| 2017 NEC |
| |
| CLASSIFICATION OF WORK: |
| BUILDING CLASSIFICATION: VB |
| EXPOSURE CLASSIFICATION: |
| RISK CATEGORY: |
| |
| MEAN ROOF HEIGHT: STATE MRH ON ELEVATION PLAN PAGE. |
| |
| EXISTING UNDER AIR: /SF |
| EXISTING COVERED: /SF |
| NEW UNDER AIR: /SF |
| NEW COVERED: /SF |
| |
| TOTALS: UNDER AIR /SF |
| COVERED /SF |
| |
| SITE SPECIFIC DESIGN WIND LOADS PER: |
| FBC RESIDENTIAL CHPT. 3 |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). |
| |
| -OR- |
| |
| ASCE 7-16 (VULT 170MPH 3 SEC GUST / VASD 132MPH) |
| |
| |
| DESIGN WIND PRESSURES: |
| WINDOWS AND DOORS ? ZONE 4 INT. / ZONE 5 CORNER |
| (POSITVE/NEGATIVE) |
| ROOF ? ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS) |
| R301.2.1 WIND DESIGN CRITERIA. |
| BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| FROM FIGURE R301.2(4). |
| |
| 2. THE PLAN SHEET LABLED SITE PLAN IS A COPY OF THE |
| LANDSCAPE PLAN L2.0. |
| PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY |
| LOCATION OF WORK. |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE |
| SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN |
| ACCURATE AND INCLUDED BOUNDRY LINE SURVEY. |
| |
| 3. PROVIDE A SITE DRAINAGE PLAN WITH A BOUNDARY LINE |
| SURVEY PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| |
| 4. PROVIDE A SOILS REPORT. |
| R401.4 SOIL TESTS. |
| WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL |
| SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE, |
| SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE |
| LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL |
| DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE |
| THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION. |
| THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN |
| APPROVED METHOD. |
| |
| 5. PROVIDE THE FINISH FLOOR ELEVATION NON-FLOOD ZONE |
| R403.1.7.3 FOUNDATION ELEVATION. |
| ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| ALL LOCATIONS ON THE SITE. |
| |
| 6. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE) |
| R401.2COMPLIANCE. |
| PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING: |
| 1. 1.SECTIONS R401 THROUGH R404. |
| 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401 |
| THROUGH R404 LABELED MANDATORY. |
| |
| 7. PLACE THE CEILING AND WALL INSULATION R VALUE ON THE |
| PLANS. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 7. PROVIDE CIVIL DRAWINGS. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 8. PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT |
| APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020 |
| FBC, FOR THE PROPOSED DOORS. |
| FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, |
| EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 9. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY FOAM |
| INSULATION. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |
| |
| |
| |
| |