Plan Review Notes
Plan Review Notes For Permit 22020406
Permit Number 22020406
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-10 14:40:32PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: PROVISO ON PLAN PAGE A-100: A SEPERATE PERMIT
 IS REQUIRED FOR THE PERGOLA. CT
  
 1. PROVIDE A COVER SHEET. INCLUDE BUILDING DATA AND
 DESIGN CRITERIA.
 PROVIDE PROJECT DATA/DESIGN PARAMETERS:
  
 PROJECT DATA: 1&2 FAMILY DWELLING UNIT
  OCCUPANCY CLASSIFICATION R3 SFR
  SCOPE OF WORK
  
 DESIGN PARAMETERS: 2020 FBC EXISTING BUILDING
  2020 FBC RESIDENTIAL
  2017 NEC
  
 CLASSIFICATION OF WORK:
 BUILDING CLASSIFICATION: VB
 EXPOSURE CLASSIFICATION:
 RISK CATEGORY:
  
 MEAN ROOF HEIGHT: STATE MRH ON ELEVATION PLAN PAGE.
  
 EXISTING UNDER AIR: /SF
 EXISTING COVERED: /SF
 NEW UNDER AIR: /SF
 NEW COVERED: /SF
  
 TOTALS: UNDER AIR /SF
  COVERED /SF
  
 SITE SPECIFIC DESIGN WIND LOADS PER:
 FBC RESIDENTIAL CHPT. 3
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 -OR-
  
 ASCE 7-16 (VULT 170MPH 3 SEC GUST / VASD 132MPH)
  
  
 DESIGN WIND PRESSURES:
 WINDOWS AND DOORS ? ZONE 4 INT. / ZONE 5 CORNER
 (POSITVE/NEGATIVE)
 ROOF ? ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS)
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 2. THE PLAN SHEET LABLED SITE PLAN IS A COPY OF THE
 LANDSCAPE PLAN L2.0.
 PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY. IDENTIFY
 LOCATION OF WORK.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDRY LINE SURVEY.
  
 3. PROVIDE A SITE DRAINAGE PLAN WITH A BOUNDARY LINE
 SURVEY PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 4. PROVIDE A SOILS REPORT.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOILS CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 5. PROVIDE THE FINISH FLOOR ELEVATION NON-FLOOD ZONE
 R403.1.7.3 FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
  
 6. PROVIDE AN ENERGY SUBMITTAL RESIDENTIAL (RE)
 R401.2COMPLIANCE.
 PROJECTS SHALL COMPLY WITH ONE OF THE FOLLOWING:
 1. 1.SECTIONS R401 THROUGH R404.
 2. 2.SECTION R405 AND THE PROVISIONS OF SECTIONS R401
 THROUGH R404 LABELED MANDATORY.
  
 7. PLACE THE CEILING AND WALL INSULATION R VALUE ON THE
 PLANS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 7. PROVIDE CIVIL DRAWINGS.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA, APPROVED UNDER THE 2020
 FBC, FOR THE PROPOSED DOORS.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 9. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY FOAM
 INSULATION.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  