Plan Review Notes For Permit 22020405 |
Permit Number |
22020405 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-08-02 13:06:01 | FIRE REVIEW COMMENTS: | | | | THE PLAN WAS REVIEWED AND FAILED WITH THE FOLLOWING. | | | | (1) THE SUBMITTED PLAN INDICATES 303 BANYAN BOULEVARD | | AND 285 BANYAN BOULEVARD. THE SUBMITTED APPLICATION | | LISTS 345 BANYAN BOULEVARD. PLEASE CORRECT AND CLARIFY | | THE CORRECT ADDRESS. | | | | (2) PROVIDE A MORE DETAILED PLAN INDICATING THE | | GENERATOR EXHAUST IN RELATION TO PROPERTY LINES, | | BUILDING WINDOWS AND DOORS, ETC. NFPA 1, 1.14 | | | | (3) PROVIDE INDICATION OF EMERGENCY AND STANDBY POWER | | STATUS INDICATORS TO BE LOCATED IN THE BUILDING | | EMERGENCY COMMEND CENTER. NFPA 1, 11.9.5 | | | | (4) INDICATE ANY DOOR OPENINGS AND THE REQUIRED FIRE | | RESISTANCE RATING AND SELF- CLOSING DEVICES IF | | APPLICABLE. NFPA 37, 6.3.5.2 | | | | (5) PROVIDE DETAILS FOR THE FILLING OF THE DIESEL FUEL | | TANK AND ANY ASSOCIATED PIPING. NFPA 37, 6.6 | | | | (6) CONFIRM THE REQUIRED FIRE SEPARATION OF THE | | GENERATOR ROOM FROM THE REST THE BUILDING. NFPA 110 | | 7.2.1 | | | | WHEN RESPONDING EITHER REPLY IN A NARRATIVE FORM TO THE | | ITEMS LISTED OR CLOUDED ON A PLAN SHEET. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|