2022-04-01 11:26:14 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22020357 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| NOTE: |
| ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING. |
| SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION |
| ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1-LOT DRAINAGE: PROPOSED ADDITION (AND POOL) AFFECTS |
| THE LOT DRAINAGE. PROVIDE DRAINAGE PLAN SHOWING HOW THE |
| SURFACE DRAINAGE IS KEPT WITHIN THE LOT AND NOT |
| DIVERTED TO ADJACENT PROPERTIES. PROVIDE DRAINAGE PLAN |
| SHOWING COMPLIANCE WITH THE FOLLOWING SECTIONS: R401.3 |
| FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS AND SEC. |
| 110.9 CITY AMENDMENTS. |
| NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED |
| GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM |
| ADJACENT PROPERTIES. |
| |
| 2-PRODUCT APPROVALS |
| 12-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)EXTERIOR DOORS. |
| B)WINDOWS. |
| C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| D)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION |
| SCHEDULE. SEE CITY SAMPLE. |
| E)METAL ROOF. |
| F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS FOR METAL |
| ROOFING. |
| G)SLEEPING PORCH UNDERLAYMENT FOR CERAMIC TILE AS |
| SPECIFIED ON PLANS. |
| |
| 3- WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| PROTECTION IF REQUIRED. |
| |
| 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| ALUMINUM TRELLIS CONSTRUCTION. SPECIFY ALL FRAMING |
| MEMBERS AND CONNECTOR AT EACH END. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| 5- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON THE |
| EXTERIOR ELEVATIONS DON'T MATCH DESIGN PRESSURES |
| SPECIFIED BY THE ENGINEER OF RECORD ON SHEET S1. REVISE |
| AS REQUIRED. SEC. R301.2.1 FBC-RESIDENTIAL. |
| NOTE: COORDINATE WITH ITEM #6 BELOW. |
| |
| 6- ENGINEER OF RECORD TO REVISE END ZONE DIMENSION |
| SPECIFIED UNDER WIND DESIGN CRITERIA ON SHEET S1. THE |
| MINIMUM DIMENSION IS 4'-0" NOT 3'-0" AS REQUIRED BY |
| NOTE "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL. REVISE AS |
| REQUIRED. |
| |
| 7- ENGINEER OF RECORD TO PROVIDE SPECIFICATIONS FOR THE |
| CONCRETE SLAB VAPOR BARRIER AS REQUIRED BY SEC. |
| R506.2.3 FBC-RESIDENTIAL. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |