Plan Review Notes
Plan Review Notes For Permit 22020255
Permit Number 22020255
Review Stop B
Sequence Number 3
Notes
Date Text
2022-03-11 12:19:34JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1 PLEASE CLARITY ROOFING SYSTEM USED.
 THE TWO SYSTEMS PROPOSED ARE NOT APPROVED FOR USE WITH
 EACH OTHER.
 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 SUBMITTED PRODUCT APPROVAL FL11288-R19 IS NOT AN
 APPROVED FLAT ROOF SYSTEM, IT IS APPROVED FOR USE AS AN
 UNDERLAYMENT. (IF APPLICABLE).
 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL15027-R7 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-8 TO
 INCLUDE LIMITATIONS PAGE(S), TECHNICAL BULLENTIN-110
 PAGES 1-2. THE EVALUATION REPORTS & TECHNICAL
 BULLENTIN-110 CAN BE PRINTED FROM THE SUMMARY OF
 PRODUCTS LOCATED AT THE BOTTOM OF THE COVER PAGE. (IF
 APPLICABLE)
 4. FBC B 107.2.1 PROVIDE CERTIFICATION THAT
 REQUIREMENTS OF 4.4.1 OF THE EVALUATION REPORT PAGE #4
 OF PRODUCT APPROVAL FL15027.2 HAS BEEN MET & IDENTIFY
 SYSTEM USED FROM TABLE 1, TABLE 1A OR TABLE 2 PAGES
 4-5. (IF APPLICABLE)
 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  