2022-03-03 09:51:45 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| PLEASE ADDRESS PREVIOUS COMMENTS BELOW DATED 2/08/2022 |
| AND RESUBMIT. |
| |
| 1. FBC B 107.2.1 PLEASE CLARITY ROOFING SYSTEM USED. |
| THE TWO SYSTEMS PROPOSED ARE NOT APPROVED FOR USE WITH |
| EACH OTHER. |
| 2. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE |
| USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| SUBMITTED PRODUCT APPROVAL FL11288-R19 IS NOT AN |
| APPROVED FLAT ROOF SYSTEM, IT IS APPROVED FOR USE AS AN |
| UNDERLAYMENT. (IF APPLICABLE). |
| 3. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL |
| FL15027-R7 IS INCOMPLETE, PROVIDE THE FOLLOWING |
| ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-8 TO |
| INCLUDE LIMITATIONS PAGE(S), TECHNICAL BULLENTIN-110 |
| PAGES 1-2. THE EVALUATION REPORTS & TECHNICAL |
| BULLENTIN-110 CAN BE PRINTED FROM THE SUMMARY OF |
| PRODUCTS LOCATED AT THE BOTTOM OF THE COVER PAGE. (IF |
| APPLICABLE) |
| 4. FBC B 107.2.1 PROVIDE CERTIFICATION THAT |
| REQUIREMENTS OF 4.4.1 OF THE EVALUATION REPORT PAGE #4 |
| OF PRODUCT APPROVAL FL15027.2 HAS BEEN MET & IDENTIFY |
| SYSTEM USED FROM TABLE 1, TABLE 1A OR TABLE 2 PAGES |
| 4-5. (IF APPLICABLE) |
| 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW |
| SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |