Plan Review Notes
Plan Review Notes For Permit 22020251
Permit Number 22020251
Review Stop B
Sequence Number 8
Notes
Date Text
2023-07-07 18:19:12ROOFING BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020251
 201 DYER RD (TERRACE)
  
 PREVIOUS COMMENT FROM PREVIOUS PLAN REVIEWER:
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-4;
 EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (170), IS NOT CORRECT. THE CORRECT
 EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D. PLEASE
 SELECT THE CORRECT OPTIONS. PRODUCT APPROVAL
 FL16709-R10 WILL NOT SATISFY EXPOSURE CATEGORY D
 ENCLOSED AREAS WITHOUT USING INSULATION.
  
 RESPONSE:
 ENGINEERING CALCULATIONS SUBMITTED:
 A)ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, THIS
 BUILDING IS LOCATED IN EXPOSURE "D" NOT "C". ENGINEER
 TO REVISE CALCULATIONS AS REQUIRED. (REPEAT COMMENT
 FROM PREVIOUS PLAN REVIEWER).
  
 B)PROVIDE ROOF SKETCH SHOWING THE DIMENSIONS FOR EACH
 NEW ROOF ZONE.
 FIGURE R301.2(7)FBC-RESIDENTIAL. SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 C)ENGINEER'S DIGITAL SIGNATURE DOESN'T COMPLY WITH THE
 REQUIREMENTS OF FBPE. NEED A SEPARATE TEXT BOX WITH THE
 TEXT BOX LANGUAGE IDENTICAL TO THE SAMPLES SHOWN BY
 FBPE.
 SEE FBPE.ORG/LEGAL/SIGNING-AND-SEALING-ENGINEERING-DOCU
 MENTS/ AND REVISE DIGITAL SIGNATURE AS REQUIRED.
 NOTE: THIS WAS CONFIRMED WITH THE FBPE INVESTIGATOR.
  
 2-DESIGNER OF RECORD FOR MASTER PERMIT NEEDS TO REVIEW
 AND APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  