Plan Review Notes For Permit 22020251 |
Permit Number |
22020251 |
|
Review Stop |
B |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2022-08-24 09:46:32 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5 | | EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (15 H < | | 20); ULTIMATE WIND SPEED (180). ZONE 3 IS MARKED ?N/A? | | WHICH INDICATES SYSTEM IS ?NOT APPLICABLE? TO ZONE1 | | PRIME DESIGN PRESSURE REQUIREMENTS AND CANNOT BE USED. | | PLEASE PROVIDE 2020 CODE VERSION PRODUCT APPROVAL/NOA | | THAT MEETS OR EXCEEDS DESIGN PRESSURE REQUIREMENTS FOR | | EXPOSURE D AREAS. SIGNED AND SEALED NAILING | | CALCULATIONS MAY BE REQUIRED. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|