2022-02-24 11:21:37 | ELECTRIC REVIEW FAILED |
| 1)ELECTRIC SERVICE RISER DETAILS 4/0 AL CONDUCTORS FOR |
| 200-AMP PANEL AND 2/0 AL CONDUCTORS TO A 150-AMP PANEL. |
| NEC 310.15.(B)(7)(2) STATES FEEDER CONDUCTORS SERVING |
| THE ENTIRE LOAD BE ABLE TO BE REDUCED TO 83% AMPACITY. |
| THE FEEDER CONDUCTORS DETAILED DO NOT CARRY THE ENTIRE |
| LOAD OF THE SERVICE THEREFORE MUST BE SIZED TO SERVE |
| THE LOAD NEC 215.29A)(1)(B) THE MINIMUM FEEDER |
| CONDUCTOR SIZE SHALL HAVE AN ALLOWABLE AMPACITY NOT |
| LESS THAN THE MAXIMUM LOAD TO BE SERVED AFTER THE |
| APPLICATION OF ANY ADJUSTMENT OR CORRECTION FACTORS. |
| 2) DRAWINGS DO NOT DETAIL ELECTRIC PANEL OR POOL AND |
| SPA EQUIPMENT LOCATIONS. PLEASE ALL ELECTRIC SUB PANEL |
| LOCATIONS AND CONDUCTOR SIZE SERVING LOADS. FBC 107.2 |
| 3) LOAD CALCULATION DOES NOT DETAIL AND POOL AND SPA |
| LOADS. PLEASE SHOW ALL LOADS WHETHER THEY ARE EXISTING |
| OR NEW. NEC 215.5 FBC 107.3 |
| 4) PLEASE DETAIL CIRCUITS TO BE GFI OR ARC FAULT |
| PROTECTED. A NOTE WILL SUFFICE. NEC 210.8 NEC 210.12 |
| AND NEC 406.4 |
| 5) IT APPEARS THE RECEPTACLE SPACING AT KITCHEN COUNTER |
| AREAS DO NOT MEET THE REQUIREMENTS AS PER NEC 210.52. |
| PLEASE CORRECT AS NECESSARY |
| 6)PLEASE DETAIL SMOKE AND CARBON MONOXIDE DETECTORS AS |
| REQUIRED PER FBC R315.1 |
| 7) PLEASE DETAIL RECEPTACLES TO BE TAMPER RESISTANT AS |
| PER NEC 406.12 AND NEC 406.4(D)(5). A NOTE WILL SUFFICE |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |