2022-02-12 12:18:39 | 2ND REVIEW FBC-2020 RES. GAS |
| PERMIT- 22020184 |
| 2/12/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| PLEASE ADDRESS PREVIOUS PLANS EXAMINERS COMMENTS. |
| |
| 1) THIS APPEARS TO BE A NEW INSTALLATION OF A GAS-FIRED |
| TANKLESS WATER HEATER AND NOT A REPLACEMENT. WPB |
| BUILDING DEPT. RECORDS TO NOT SHOW A PREVIOUS GAS |
| PERMIT WAS ISSUED FOR A TANKLESS WATER HEATER. PLEASE |
| PROVIDE A COMPLETE GAS RISER DRAWING THAT INCLUDES ALL |
| NEW AND EXISTING GAS PIPING AND APPLIANCES AT THE |
| RESIDENCE- SECTION G2412.3 & G2412.4 FBC RES. REFER TO |
| FBC RES. CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND BTU LOAD OF THE WATER HEATER AND |
| OTHER EXISTING APPLIANCES. |
| D) TYPE AND SIZE OF PIPING SUPPLYING THE WATER HEATER. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) PIPE SIZING TABLES. |
| |
| 2) PROVIDE A DRAWING THAT SHOWS THE LOCATION OF THE |
| WATER HEATER AND REQUIRED CLEARANCES PER MANUFACTURER'S |
| SPECIFICATIONS AND SECS. G2427.8 & G2448.1 FBC RES |
| |
| 3) IF AN ELECTRICAL OUTLET HAS TO BE INSTALLED FOR THE |
| NEW TANKLESS WATER HEATER, AND ELECTRICAL PERMIT IS |
| REQUIRED FOR THIS NEW ELECTRICAL WORK. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |