Plan Review Notes
Plan Review Notes For Permit 22020132
Permit Number 22020132
Review Stop B
Sequence Number 2
Notes
Date Text
2022-05-17 11:26:42NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020132
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE SUBMITTED AND CERTIFIED
 BY THE OWNER OR AUTHORIZED AGENT BEFORE ISSUING THE
 PERMIT.
  
 ORIGINAL COMMENT:
 1- ROOF SHEATHING NAILING SPACING SPECIFIED ON SHEET
 S-2 DOESN'T COMPLY WITH TABLE R803.2.3.1
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 RESPONSE:
 REVISED ROOF SHEATHING NAILING SPECIFICATIONS IS
 MISSING SPECIFICATIONS FOR ROOF ZONE 2N.
  
 2- OK.
 3- OK.
  
 ORIGINAL COMMENT:
 4-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 ORIGINAL COMMENT:
 5- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)SINGLE HUNG WINDOWS.
 B)ENTRY DOOR.
 C)GREAT ROOM SWING DOOR.
 D)ROOF SHINGLES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. CONTRACTOR TO RESPOND IF
 SUBMITTING LATER AS A DEFERRED SUBMITTAL OR IF
 SUBMITTING THEM AT RESUBMITAL.
  
 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT
 ON SHEET A-1 WITH PRODUCT APPROVALS SUBMITTED TO AVOID
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 7- DRAINAGE PLAN DRAWING C-1: REVISE PROPOSED DRAINAGE
 AT THE REAR AND RIGHT HAND SIDE OF THE PROPERTY.
 SURFACE DRAINAGE CAN NOT BE DIVERTED TO ADJACENT
 PROPERTIES. DRAINAGE WATER TO BE KEPT WITHIN THE LOT OR
 DIVERTED TOWARDS THE STREET. R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY
 AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. DRAINAGE PLAN WAS NOT
 REVISED. CONTRACTOR TO RESPOND IF SUBMITTING LATER AS A
 DEFERRED SUBMITAL OR IF SUBMITTING REVISED DRAINAGE
 PLAN AT RESUBMITAL.
  
 8- OK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  