2022-04-14 13:52:08 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22020132 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| ***IMPORTANT*** |
| ENERGY CALCULATIONS NEED TO BE SUBMITTED AND CERTIFIED |
| BY THE OWNER OR AUTHORIZED AGENT BEFORE ISSUING THE |
| PERMIT. |
| |
| 1- ROOF SHEATHING NAILING SPACING SPECIFIED ON SHEET |
| S-2 DOESN'T COMPLY WITH TABLE R803.2.3.1 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| 2- GABLE END UPLIFT DIAGRAM SHOWN ON SHEET S-2 DOESN'T |
| MATCH ROOF ZONES ZONES SPECIFIED ON FIGURE R301.2(7) |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| 3- PLANS DON'T PROVIDE SPECIFICATIONS SHOWING HOW |
| COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR |
| ROOFING UNDERLAYMENT SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001 |
| |
| 4-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| R101.5 FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 5- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)SINGLE HUNG WINDOWS. |
| B)ENTRY DOOR. |
| C)GREAT ROOM SWING DOOR. |
| D)ROOF SHINGLES. |
| |
| 6- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| NOTE: COORDINATE PRODUCT APPROVAL SUBMITTAL AFFIDAVIT |
| ON SHEET A-1 WITH PRODUCT APPROVALS SUBMITTED TO AVOID |
| CONFLICTS/DELAYS. |
| |
| 7- DRAINAGE PLAN DRAWING C-1: REVISE PROPOSED DRAINAGE |
| AT THE REAR AND RIGHT HAND SIDE OF THE PROPERTY. |
| SURFACE DRAINAGE CAN NOT BE DIVERTED TO ADJACENT |
| PROPERTIES. DRAINAGE WATER TO BE KEPT WITHIN THE LOT OR |
| DIVERTED TOWARDS THE STREET. R401.3 FBC-RESIDENTIAL. |
| SEC. 107.2.5 CITY AMENDMENTS AND SEC. 110.9 CITY |
| AMENDMENTS. |
| |
| 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS |
| UPDATED TO $154,371.00. THE PERMIT FEE BALANCE IS |
| $2884.68. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |