2022-06-16 15:57:36NEW SINGLE FAMILY RESIDENCE (R3) 4TH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22020124
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
 1- OK.
 2- OK.
 3-OK.
 4-OK.
 5- OK.
  
 ORIGINAL COMMENT:
 6- WIND DESIGN INFORMATION ON SHEET A-1 IS NOT CLEAR.
 ULTIMATE WIND SPEED AND NOMINAL WIND SPEED UNDER WALL
 PRESSURES DON'T MATCH THE ULTIMATE WIND SPEED AND
 NOMINAL WIND SPEED UNDER WIND DESIGN BASIS SHOWN ON THE
 SAME SHEET. REVISE/CLARIFY AS REQUIRED. WHICH ONE IS
 THE CORRECT DESIGN CRITERIA FOR THIS HOUSE? SEC.
 R301.2.1 FBC-RESIDENTIAL.
 NOTES: REVISE WINDOWS/DOORS DESIGN PRESSURES
 ACCORDINGLY TO AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 7- ENERGY CALCULATIONS:
  
 ORIGINAL COMMENT:
 (A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)ROOF TYPE SPECIFIED ON PAGE 2 DOESN'T MATCH PLANS.
 THIS IS A HIP ROOF. REVISE AS REQUIRED. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C)WINDOW OVERHANG DEPTH AND SEPARATION INFORMATION
 SHOWN ON PAGE 3 DOESN'T MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED TO MATCH.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) THERE ARE NO WINDOWS ON THE WEST SIDE FOR THIS
 HOUSE. BATHROOM WINDOW IS ON THE EAST SIDE. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 8- PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)SINGLE HUNG WINDOWS. NOA 17-1212.21 SUBMITTED EXPIRED
 ON DECEMBER 27,2021. NEED CURRENT NOA.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B)THERMA-TRU ENTRY AND REAR SWING DOOR. FLORIDA PRODUCT
 APPROVAL FL8871 SUBMITTED IS FOR THE PREVIOUS CODE
 CYCLE. NEED TO PROVIDE CURRENT PRODUCT APPROVAL. ALSO,
 DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED TO
 PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL, INCLUDING
 THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO THE DRAWINGS SUBMITTED. THE FLORIDA
 PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS IF
 PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. CHAPTER
 553 F.S.
  
 RESPONSE:
 PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE FOR NEW
 DOOR PRODUCT APPROVAL FL-21138.1 SUBMITTED.
  
 9-PRODUCT APPROVAL REVIEW/APPROVAL. SEC. 107.3.4.1 CITY
 AMENDMENTS.
 DESIGNER OF RECORD TO REVISE THE PRODUCT APPROVAL
 SUBMITTAL AFFIDAVIT (SEC. 107.3.4.1 CITY AMENDMENTS) ON
 SHEET A-1 TO MATCH PRODUCT APPROVALS SUBMITTED:
  
 ORIGINAL COMMENT:
 A)SINGLE HUNG WINDOWS NOA DOESN'T MATCH NOA SUBMITTED.
 NOTE: COORDINATE WITH ITEM #8(A) ABOVE TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT.
 10- DRAINAGE PLAN DRAWING C-1:
 A) REVISE PROPOSED DRAINAGE AT THE REAR OF THE
 PROPERTY. SURFACE DRAINAGE CAN NOT BE DIVERTED TO
 ADJACENT PROPERTIES. DRAINAGE WATER TO BE KEPT WITHIN
 THE LOT OR DIVERTED TOWARDS THE STREET. R401.3
 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS AND SEC.
 110.9 CITY AMENDMENTS.
  
 B)PARCEL ID IS INCORRECT. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  