Plan Review Notes
Plan Review Notes For Permit 22020124
Permit Number 22020124
Review Stop B
Sequence Number 3
Notes
Date Text
2022-05-12 13:40:21PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 2B.) THE ROOF SHEATHING NAILING SPACING SPECIFICATIONS
 ON SHEET S-2 AT THE SIDE OF ROOF DIAGRAMS IS MISSING
 ZONE 2N.
 6.) THE WIND DESIGN INFORMATION (ULTIMATE WIND SPEED &
 NOMINAL WIND SPEED) ON PLAN SHEET A-1 AT WALL PRESSURES
 NEEDS TO BE CHANGED TO MATCH THE ULTIMATE & NOMINAL
 WIND SPEED) SHOWN UNDER WIND DESIGN BASIS.
 7D.) THERE ARE NO WINDOWS ON THE WEST SIDE OF HOUSE, AS
 INDICATED ON PAGE 3 OF THE SUMMARY CHECKLIST FORM
 R405-2020. THE CHECKLIST AND/OR PLAN SHEETS NEED TO BE
 CORRECTED.
 7E.) THE BUILDER NEEDS TO COMPLETE AND SIGN THE EPL
 DISPLAY CARD.
 8A.) SINGLE HUNG WINDOW NOA 17-1212.21 HAS EXPIRED.
 PROVIDE A CURRENT NOA.
 8B.) THERMA TRU DOOR PRODUCT APPROVAL # FL 8871 WAS FOR
 THE LAST CODE CYCLE. PROVIDE CURRENT PRODUCT APPROVAL.
 ALSO INCLUDE THE COVER PAGE THAT CORRESPONDS TO THE
 SUBMITTED DRAWINGS.
 9A.) THE AFFIDAVIT OF PRODUCT APPROVALS FROM PLAN SHEET
 A-1 DOES NOT MATCH THE SINGLE HUNG WINDOW NOA THAT WAS
 SUBMITTED.
 9B.) THE AFFIDAVIT OF PRODUCT APPROVALS FROM PLAN SHEET
 A-1 DOES NOT MATCH THE DOOR PRODUCT APPROVAL THAT WAS
 SUBMITTED.
 9C.) THE ROOF HIP AND RIDGE NOA ON PLAN SHEETS DOES NOT
 MATCH THE SUBMITTED NOA.
  
  
  