2022-04-14 17:22:09 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22020124 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| ***IMPORTANT*** |
| ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER |
| OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT. |
| |
| 1- OK. |
| |
| ORIGINAL COMMENT: |
| 2-ROOF SHEATHING NAILING SPACING SPECIFIED ON SHEET S-2 |
| DOESN'T COMPLY WITH TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| REVISE AS REQUIRED. |
| |
| RESPONSE: |
| (A)REPEAT COMMENT. ROOF SHEATHING NAILING SPACING |
| SPECIFICATIONS SHOWN ON THE RIGHT HAND SIDE OF ROOF |
| DIAGRAMS STILL DON'T COMPLY WITH TABLE R803.2.3.1 |
| FBC-RESIDENTIAL. SEE TABLE AND REVISE AS REQUIRED. |
| |
| (B)ROOF SHEATHING NAILING SPACING SPECIFICATIONS SHOWN |
| ON THE RIGHT HAND SIDE OF ROOF DIAGRAMS IS MISSING ROOF |
| ZONE 2N. |
| SEC. R803.2.3.1 FBC-RESIDENTIAL. |
| |
| (C)ROOF SHEATHING NAILING SPACING SPECIFICATIONS SHOWN |
| ON THE RIGHT HAND SIDE OF ROOF DIAGRAMS ARE SHOWING TWO |
| DIFFERENT NAILING SPACING SPECIFICATIONS FOR ROOF ZONE |
| 2E AND 2R. THIS IS NO CLEAR. PROVIDE ONLY ONE NAILING |
| SPECIFICATION TO AVOID CONFLICTS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 3-OK. |
| 4-OK. |
| |
| ORIGINAL COMMENT. NOT ADDRESSED. |
| 5-DETAIL 3 ON SHEET A-3 IS MISSING SPECIFICATIONS FOR |
| THE WALL CONSTRUCTION MATERIALS: |
| A)NEED TO SPECIFY WALL SHEATHING AND FASTENING. SEC. |
| R703.1.2 FBC-RESIDENTIAL. |
| |
| B) NEED TO SPECIFY STUCCO BASE (LATH OR ANY OTHER |
| STUCCO BASE) AS REQUIRED BY SEC. R703.7 FBC-RESIDENTIAL |
| AND TABLE R702.1(1) FBC-RESIDENTIAL. |
| |
| C)NEED TO SPECIFY TWO WATER RESISTIVE BARRIERS WHEN |
| STUCCO IS APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3 |
| FBC-RESIDENTIAL. |
| |
| D)NEED TO SPECIFY THE MIN. STUCCO THICKNESS AS REQUIRED |
| BY SEC. R703.7 FBC-RESIDENTIAL AND TABLE R702.1(1) |
| FBC-RESIDENTIAL. |
| |
| |
| ORIGINAL COMMENT: |
| 6- WIND DESIGN INFORMATION ON SHEET A-1 IS NOT CLEAR. |
| ULTIMATE WIND SPEED AND NOMINAL WIND SPEED UNDER WALL |
| PRESSURES DON'T MATCH THE ULTIMATE WIND SPEED AND |
| NOMINAL WIND SPEED UNDER WIND DESIGN BASIS SHOWN ON THE |
| SAME SHEET. REVISE/CLARIFY AS REQUIRED. WHICH ONE IS |
| THE CORRECT DESIGN CRITERIA FOR THIS HOUSE? SEC. |
| R301.2.1 FBC-RESIDENTIAL. |
| NOTES: REVISE WINDOWS/DOORS DESIGN PRESSURES |
| ACCORDINGLY TO AVOID CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| ORIGINAL COMMENT. NOT ADDRESSED. |
| 7- ENERGY CALCULATIONS: |
| (A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE |
| CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S |
| ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| B)ROOF TYPE SPECIFIED ON PAGE 2 DOESN'T MATCH PLANS. |
| THIS IS A HIP ROOF. REVISE AS REQUIRED. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| C)WINDOW OVERHANG DEPTH AND SEPARATION INFORMATION |
| SHOWN ON PAGE 3 DOESN'T MATCH PLANS. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. REVISE AS REQUIRED TO MATCH. |
| |
| D) THERE ARE NO WINDOWS ON THE WEST SIDE FOR THIS |
| HOUSE. BATHROOM WINDOW IS ON THE EAST SIDE. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| ORIGINAL COMMENT. NOT ADDRESSED. |
| 8- PRODUCT APPROVALS |
| PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001 |
| FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)SINGLE HUNG WINDOWS. NOA 17-1212.21 SUBMITTED EXPIRED |
| ON DECEMBER 27,2021. NEED CURRENT NOA. |
| |
| B)THERMA-TRU ENTRY AND REAR SWING DOOR. FLORIDA PRODUCT |
| APPROVAL FL8871 SUBMITTED IS FOR THE PREVIOUS CODE |
| CYCLE. NEED TO PROVIDE CURRENT PRODUCT APPROVAL. ALSO, |
| DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED TO |
| PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL, INCLUDING |
| THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT |
| CORRESPONDS TO THE DRAWINGS SUBMITTED. THE FLORIDA |
| PRODUCT APPROVAL IS REQUIRED BECAUSE IT SHOWS IF |
| PRODUCT IS APPROVED AND CURRENT CODE IN EFFECT. CHAPTER |
| 553 F.S. |
| |
| 9-PRODUCT APPROVAL REVIEW/APPROVAL. SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| DESIGNER OF RECORD TO REVISE THE PRODUCT APPROVAL |
| SUBMITTAL AFFIDAVIT (SEC. 107.3.4.1 CITY AMENDMENTS) ON |
| SHEET A-1: |
| A)SINGLE HUNG WINDOWS NOA DOESN'T MATCH NOA SUBMITTED. |
| NOTE: COORDINATE WITH ITEM #8(A) ABOVE TO AVOID |
| CONFLICTS/DELAYS. |
| |
| B)THERMA-TRU ENTRY AND REAR SWING DOOR FLORIDA PRODUCT |
| APPROVAL NUMBER DOESN'T MATCH FLORIDA PRODUCT APPROVAL |
| SUBMITTED. |
| NOTE: COORDINATE WITH ITEM #8(B) ABOVE TO AVOID |
| CONFLICTS/DELAYS. |
| |
| C)ROOF HIP AND RIDGE NOA DOESN'T MATCH NOA SUBMITTED. |
| |
| ORIGINAL COMMENT. NOT ADDRESSED. |
| 10- DRAINAGE PLAN DRAWING C-1: |
| A) REVISE PROPOSED DRAINAGE AT THE REAR OF THE |
| PROPERTY. SURFACE DRAINAGE CAN NOT BE DIVERTED TO |
| ADJACENT PROPERTIES. DRAINAGE WATER TO BE KEPT WITHIN |
| THE LOT OR DIVERTED TOWARDS THE STREET. R401.3 |
| FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS AND SEC. |
| 110.9 CITY AMENDMENTS. |
| |
| B)PARCEL ID AND STREET ADDRESS ARE INCORRECT. REVISE AS |
| REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |