Plan Review Notes For Permit 22020114 |
Permit Number |
22020114 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-03 11:14:55 | THE SITE PLAN DOES NOT PROVIDE ENOUGH SPECIFIC LOCATION | | DETAIL TO PROPERLY DISCERN COMMENTS APPLICABLE TO | | INSTALLATION. | | | | PLEASE INCLUDE A PLAN THAT INCLUDES THE LAYOUT OF THE | | TENT, INCLUDING EXITS, EXIT SIGNS, FIRE EXTINGUISHERS, | | AND EGRESS PATHS. | | | | PER FL STATUTE 633.202; PROVIDE PORTABLE FIRE | | EXTINGUISHERS. EXTINGUISHERS SHALL HAVE A MINIMUM | | RATING OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED | | FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO | | EXTINGUISHERS SHALL NOT EXCEED 75 FEET. PROVIDE TYPE K | | EXTINGUISHERS WHEN COOKING WITH GREASE OR WHEN | | PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | BUILDING STRUCTURES. | | | | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | LOCATIONS. | | | | LT. BRIAN DOLAN | | DIVISION OF FIRE PREVENTION | | 561-804-4752 | | [email protected] | | | | | | |
|