2022-02-03 10:26:05 | BUILDING PLAN REVIEW TENTS |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| REVISED 1ST REVIEW 2-4-22. CT |
| |
| RESULTS: DENIED |
| |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| |
| NOTICE: THE TENT TIE DOWN (2020 FBC) AND ENG CALC'S |
| (ASCE 7-16) FOR THE THE 50X115 TENT (15MX35M) ARE |
| APPROVED. (VALID SIG AND SEAL REQUIRED-SEE SIGNATURE |
| REVIEW COMMENTS) |
| |
| 1. PROVIDE A TENT TIE DOWN DETAIL FOR THE 10X20 TENT |
| (NOT SUBMITTED FOR REVIEW). |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. PROVIDE A TENT TIE DOWN DETAIL, (APPROVED UNDER 2020 |
| FBC) FOR THE 20X30 TENT (EXPIRED) |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| HOUSE KEEPING: KEEP THE DOCUMENTS SEPERATE FOR EACH |
| TENT. (TIE DOWN DETAILS AND/OR WIND LOADS). I CANNOT |
| REMOVE INDIVIDUAL SHEETS FROM A MULTI-PAGE PDF) |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| NOTICE: REGENCY PARTY RENTALS; RENA TOPPE; PLEASE |
| SUBMIT THE SAME DOCUMENTS SUBMITTED LAST YEAR FOR THE |
| GREEK FESTIVAL UNDER PERMIT 20011146 |
| |
| APPLICANTION CHECKLIST |
| ALL STRUCTURES INSTALLED FOR LESS THAN 180 DAYS, |
| GREATER THAN 120 SQ. FT. WITH 10 OR MORE OCCUPANTS |
| * APPLICATION NEEDS TO BE SUBMITTED AT LEAST TWO WEEKS |
| PRIOR TO EVENT |
| 1. PERMIT APPLICATION |
| A. PROVIDE EVENT FUNCTION |
| B. ADDRESS OF EVENT |
| C. WORK DESCRIPTION ? I.E. NUMBER AND SIZE OF TENTS |
| D. OWNER AND CONTRACTOR INFO. |
| E. VALUE ? ATTACH COPY OF CONTRACT WITH OWNER |
| F. SPECIFY DATES OF INSTALLATION AND REMOVAL |
| 2. SITE PLAN |
| A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW |
| CONSTRUCTION AND EXISTING |
| STRUCTURES ON THE SITE? |
| B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER |
| FBC CHPT. 6, SEC. 602 |
| C. PROVIDE SQUARE FOOTAGE |
| D. PROVIDE ESTIMATED OCCUPANCY OF EACH TENT |
| E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT |
| ENTRANCE |
| F. IDENTIFY MEANS OF EGRESS PER CHPT. 10 |
| G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE |
| RESTROOMS |
| H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500 |
| FEET OF TENT |
| 2. FOUNDATION/TIE DOWN |
| A. PROVIDE DETAIL OF TIE DOWN FOR UPLIFT |
| B. PROVIDE DETAIL OF ANCHORS FOR TENT LEG LATERAL |
| MOVEMENT |
| 3. CONFORMANCE PER SECTION 3103.1.1 |
| TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, |
| ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY |
| REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE PUBLIC |
| HEALTH, SAFETY AND GENERAL WELFARE. |
| A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR |
| STRUCTURES WITH SPANS OF 30 FEET OR GREATER. |
| B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER |
| NFPA 701 FOR EACH TENT |
| C. MEANS OF EGRESS 1) OPEN SIDES ? NO LIFE SAFETY PLAN |
| REQUIRED. |
| 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN |
| A) STATE OCCUPANT LOAD. |
| B) IDENTIFY MEANS OF EGRESS. |
| C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO |
| EXIT. |
| D) PROVIDE FLOOR LAYOUT OF EVENT. |
| D. ACCESSIBILITY 1) IDENTIFY ACCESSIBLE ROUTE ON SITE |
| PLAN |
| E. LIGHT 1) OPEN SIDES ? N/A |
| 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE |
| F. VENTILATION 1) OPEN SIDES ? N/A |
| 2) CLOSED SIDES ? PER SEC. 1203 |
| G. SANITARY 1) IDENTIFY EXISTING PERMANENT FACILITIES |
| ON SITE PLAN |
| 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902. |
| _______________________________________________________ |
| _________________ |
| |
| |
| *ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| OF 30 FEET OR GREATER IN ANY DIRECTION: |
| |
| A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| BASEPLATE/TIEDOWN DETAILS. |
| B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| |
| THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| A DESIGN PROFESSIONAL. |
| |
| OPTION TO ABOVE REQUIREMENT ? |
| YOU MAY PLACE A STATEMENT ON YOUR PLAN THAT THE TENT |
| WILL BE REMOVED IF WINDS ARE EXPECTED TO EXCEED 30 MPH |
| |
| _______________________________________________________ |
| _________________ |
| |
| |
| **ADDITIONAL REQUIREMENTS** |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A SPAN |
| OF 40 FEET OR GREATER IN ANY DIRECTION: |
| |
| A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| BASEPLATE/TIEDOWN DETAILS. |
| B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE. |
| |
| THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| A DESIGN PROFESSIONAL. |
| |
| NO EXCEPTIONS BY ORDER OF THE BUILDING OFFICIAL |
| |
| _______________________________________________________ |
| _________ |
| |
| ***ADDITIONAL REQUIREMENTS |
| FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN |
| ?ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS?. |
| |
| FLORIDA STATUTE 553.79 ?THREHOLD STRUCTURE? SHALL APPLY |
| |
| A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ? WILL BE |
| PROVIDED TO APPLICANT |
| B. PROVIDE THRESHOLD INSPECTION PLAN |
| C. PROVIDE AFFIDAVIT ?CERTIFICATE OF CODE COMPLIANCE? |
| _______________________________________________________ |