Plan Review Notes
Plan Review Notes For Permit 22020100
Permit Number 22020100
Review Stop M
Sequence Number 1
Notes
Date Text
2023-01-05 09:04:56FUEL PERMIT- 22081533
 MECH. SUB FOR GENERATOR PERMIT- 22121005
  
 1ST REVIEW FMC
 PERMIT: 22020098
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE MUFFLER DETAILS INCLUDING THE MAX.
 DISTANCE OF THE EXHAUST PIPING AND PIPING SIZES. FBC
 107.3.5
  
 2) PROVIDE A SITE PLAN INDICATING THE DISTANCE FROM
 GENERATOR EXHAUST TERMINATION LOCATION TO THE PROPERTY
 LINE. FMC 501.3.1
  
 3) IN DOING THE FUEL PORT AND PIPING REVIEW FOR THIS
 PROJECT I SEE THAT A REVISED SHEET M2.02G WAS SUBMITTED
 TO SHOW THE FUEL PIPING AND FUEL PORT. THERE IS A
 REVISION 10 ON THIS DRAWING THAT SHOWS A GEF-A AND
 GEF-B. I DO NOT SEE THESE ON THE APPROVED MASTER PERMIT
 APPROVED PLANS. PLEASE SUBMIT THE REVISION FOR THE
 ADDITION OF THESE EXHAUST FANS AND EXPLAIN THE REASON
 THEY WERE ADDED IN THIS REVISION. FBC 107.3.5
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  