2023-01-05 09:04:56 | FUEL PERMIT- 22081533 |
| MECH. SUB FOR GENERATOR PERMIT- 22121005 |
| |
| 1ST REVIEW FMC |
| PERMIT: 22020098 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE THE MUFFLER DETAILS INCLUDING THE MAX. |
| DISTANCE OF THE EXHAUST PIPING AND PIPING SIZES. FBC |
| 107.3.5 |
| |
| 2) PROVIDE A SITE PLAN INDICATING THE DISTANCE FROM |
| GENERATOR EXHAUST TERMINATION LOCATION TO THE PROPERTY |
| LINE. FMC 501.3.1 |
| |
| 3) IN DOING THE FUEL PORT AND PIPING REVIEW FOR THIS |
| PROJECT I SEE THAT A REVISED SHEET M2.02G WAS SUBMITTED |
| TO SHOW THE FUEL PIPING AND FUEL PORT. THERE IS A |
| REVISION 10 ON THIS DRAWING THAT SHOWS A GEF-A AND |
| GEF-B. I DO NOT SEE THESE ON THE APPROVED MASTER PERMIT |
| APPROVED PLANS. PLEASE SUBMIT THE REVISION FOR THE |
| ADDITION OF THESE EXHAUST FANS AND EXPLAIN THE REASON |
| THEY WERE ADDED IN THIS REVISION. FBC 107.3.5 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |