Date |
Text |
2022-04-20 12:24:24 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS AN INDICATION OF EXTERIOR EXIT STAIRS, BUT |
| NO DESIGN CALL OUT OF MATERIAL, TREAD & RISERS |
| DIMENSIONS, TREAD DESIGN TO AVOID WATER BUILDUP, |
| RAILING DESIGN, ETC. THAT MEET THE REQUIREMENTS OF NFPA |
| 101, CH 7 MEANS OF EGRESS. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE. |
| |
| |
| 2) THERE ARE EXISTING WINDOWS AND A DOOR UNDER THE |
| PROPOSED TERRACE AND WITHIN 10' OF THE EXIT STAIRS. |
| |
| THOSE OPENINGS ARE REQUIRED TO BE RATED PER NFPA 101 CH |
| 7, MEANS OF EGRESS. |
| |
| 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS. |
| 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE |
| INTERIOR OF THE |
| BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE |
| RATING REQUIRED FOR |
| ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING |
| PROTECTIVES, EXCEPT AS |
| FOLLOWS: |
| (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS |
| BALCONY THAT HAS TWO |
| REMTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE PERMITTED TO |
| BE |
| UNPROTECTED. |
| (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT |
| STORIES, INCLUDING THE |
| STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED TO |
| BE UNPROTECTED |
| WHERE THERE IS A REMOTELY LOCATED SECOND EXIT. |
| (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS |
| SERVING THREE OR FEWER |
| ADJACENT STORIES, INCLUDING THE STORY WHERE THE EXIT |
| DISCHARGES, SHALL |
| BE PERMITTED TO BE UNPROTECTED WHERE THERE IS A |
| REMOTELY LOCATED |
| SECOND EXIT. |
| (4) THE FIRE RESISTANCE RATING OF A SEPARATION |
| EXTENDING 10 FT (3050 MM) |
| FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1 HOUR |
| WHERE OPEN INGS HAVE A MINIMUM 3 |
| ?4-HOUR FIRE PROTECTION RATING. |
| (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED |
| THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE |
| WITH SECTION 9.7 SHALL BE PERMITTED TO BE UNPROTECTED |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 3) THERE IS AN INDICATION OF CHANGING THE SINGLE |
| EXTERIOR DOOR TO A DOUBLE DOOR, BUT THERE IS NO |
| INDICATION OF DOOR HARDWARE, |
| |
| PLEASE PROVIDE. |
| |
| |
| 3A) IS THE EXISTING DOOR AN EXIT SPACE FROM THE 2ND |
| FLOOR SPACE AND IS THERE AN EXSITING EXIT SIGN OVER |
| THIS PROPOSED DOUBLE DOOR. |
| |
| PLEASE PROVIDE DETAILS, INCLUDING DOOR HARDWARE |
| COMPLIANT WITH EXIT DOOR HARDWARE PER NFPA 101, CH 7 |
| MEANS OF EGRESS. |
| |
| 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| READILY FROM THE |
| EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED |
| |
| 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A TOOL, |
| OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| EGRESS SIDE |
| |
| |
| 3B) THERE IS NO INDICATION OF THE INTERIOR EXISITNG |
| SPACE OCCUPANCY CLASSIFICATION. |
| |
| PLEASE PROVIDE THE EXISTING SPACE OCCUPANCY |
| CLASSIFICATION. |
| |
| |
| |
| 4) THERE ARE INDICATIONS THAT STRUCTURAL SUPPORT |
| COLUMNS ARE IN CLOSE PROXIMITY TO VEHICLE PARKING |
| SPACES. |
| |
| WHAT ARE THE PROPOSED SAFETY FEATURES TO HELP ELIMINATE |
| VEHICLE CONTACT WITH THESE SUPPORT COLUMNS. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |