Plan Review Notes
Plan Review Notes For Permit 22020076
Permit Number 22020076
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-04-20 12:24:24THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF EXTERIOR EXIT STAIRS, BUT
 NO DESIGN CALL OUT OF MATERIAL, TREAD & RISERS
 DIMENSIONS, TREAD DESIGN TO AVOID WATER BUILDUP,
 RAILING DESIGN, ETC. THAT MEET THE REQUIREMENTS OF NFPA
 101, CH 7 MEANS OF EGRESS.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE.
  
  
 2) THERE ARE EXISTING WINDOWS AND A DOOR UNDER THE
 PROPOSED TERRACE AND WITHIN 10' OF THE EXIT STAIRS.
  
 THOSE OPENINGS ARE REQUIRED TO BE RATED PER NFPA 101 CH
 7, MEANS OF EGRESS.
  
 7.2.2.6.3 SEPARATION AND PROTECTION OF OUTSIDE STAIRS.
 7.2.2.6.3.1* OUTSIDE STAIRS SHALL BE SEPARATED FROM THE
 INTERIOR OF THE
 BUILDING BY CONSTRUCTION WITH THE FIRE RESISTANCE
 RATING REQUIRED FOR
 ENCLOSED STAIRS WITH FIXED OR SELF-CLOSING OPENING
 PROTECTIVES, EXCEPT AS
 FOLLOWS:
 (1) OUTSIDE STAIRS SERVING AN EXTERIOR EXIT ACCESS
 BALCONY THAT HAS TWO
 REMTE OUTSIDE STAIRWAYS OR RAMPS SHALL BE PERMITTED TO
 BE
 UNPROTECTED.
 (2) OUTSIDE STAIRS SERVING TWO OR FEWER ADJACENT
 STORIES, INCLUDING THE
 STORY WHERE THE EXIT DISCHARGES, SHALL BE PERMITTED TO
 BE UNPROTECTED
 WHERE THERE IS A REMOTELY LOCATED SECOND EXIT.
 (3) IN EXISTING BUILDINGS, EXISTING OUTSIDE STAIRS
 SERVING THREE OR FEWER
 ADJACENT STORIES, INCLUDING THE STORY WHERE THE EXIT
 DISCHARGES, SHALL
 BE PERMITTED TO BE UNPROTECTED WHERE THERE IS A
 REMOTELY LOCATED
 SECOND EXIT.
 (4) THE FIRE RESISTANCE RATING OF A SEPARATION
 EXTENDING 10 FT (3050 MM)
 FROM THE STAIRS SHALL NOT BE REQUIRED TO EXCEED 1 HOUR
 WHERE OPEN INGS HAVE A MINIMUM 3
 ?4-HOUR FIRE PROTECTION RATING.
 (5) OUTSIDE STAIRS IN EXISTING BUILDINGS PROTECTED
 THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.7 SHALL BE PERMITTED TO BE UNPROTECTED
  
 PLEASE REVIEW AND CORRECT.
  
  
 3) THERE IS AN INDICATION OF CHANGING THE SINGLE
 EXTERIOR DOOR TO A DOUBLE DOOR, BUT THERE IS NO
 INDICATION OF DOOR HARDWARE,
  
 PLEASE PROVIDE.
  
  
 3A) IS THE EXISTING DOOR AN EXIT SPACE FROM THE 2ND
 FLOOR SPACE AND IS THERE AN EXSITING EXIT SIGN OVER
 THIS PROPOSED DOUBLE DOOR.
  
 PLEASE PROVIDE DETAILS, INCLUDING DOOR HARDWARE
 COMPLIANT WITH EXIT DOOR HARDWARE PER NFPA 101, CH 7
 MEANS OF EGRESS.
  
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE
  
  
 3B) THERE IS NO INDICATION OF THE INTERIOR EXISITNG
 SPACE OCCUPANCY CLASSIFICATION.
  
 PLEASE PROVIDE THE EXISTING SPACE OCCUPANCY
 CLASSIFICATION.
  
  
  
 4) THERE ARE INDICATIONS THAT STRUCTURAL SUPPORT
 COLUMNS ARE IN CLOSE PROXIMITY TO VEHICLE PARKING
 SPACES.
  
 WHAT ARE THE PROPOSED SAFETY FEATURES TO HELP ELIMINATE
 VEHICLE CONTACT WITH THESE SUPPORT COLUMNS.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved