2022-05-03 13:47:20 | ROOFED PATIO ADDITION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) DRAWING (A-1) SHOWS BUILDING CONSTRUCTION TYPE AS |
| IIB - PLEASE SHOW PATIO ADDITION TO COMPLY WITH FBC |
| 602.2 TYPES I AND II. |
| TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF |
| CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN |
| TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS |
| PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE. |
| |
| 2) PLEASE SHOW CEILING HEIGHT TO COMPLY WITH FBC 1208.2 |
| MINIMUM CEILING HEIGHTS. |
| OCCUPIABLE SPACES, HABITABLE SPACES AND CORRIDORS SHALL |
| HAVE A CEILING HEIGHT OF NOT LESS THAN 7 FEET 6 INCHES |
| (2286 MM) ABOVE THE FINISHED FLOOR. |
| |
| 3) PLEASE SHOW THE WIDTH BETWEEN RAILINGS TO ENTER THE |
| STAIRWAY FROM THE DECK FBC 1005.1 |
| |
| 4) PLEASE SHOW THE VERTICAL ACCESSIBILITY PER FBC A |
| 201.1.1 |
| |
| 5) THE PATIO SHOWS A 4" STEP DOWN FROM THE EXISTING |
| FLOOR ELEVATION THE DECK NEEDS TO BE ACCESSIBLE PER FBC |
| 206.2.5 RESTAURANTS AND CAFETERIAS. |
| IN RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE |
| SHALL BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED |
| OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS. |
| NOTWITHSTANDING THE REQUIREMENTS AND EXCEPTIONS OF THIS |
| SECTION, SECTION 201.1.1 SHALL APPLY. |
| |
| 6) PLEASE SHOW THE ACCESSIBLE BAR SEATING PER FBC A 226 |
| - SHOW KNEE AND TOE CLEARANCE PER FBC A CHAPTER 3 - |
| SHOW DINING BAR TOP HEIGHT PER FBC A 902 |
| |
| 7) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS - ALL |
| PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE DESIGNER OF RECORD FBC WPB 107.3.4 - |
| DOOR PRODUCT APPROVALS CAN BE ADDED TO THE DEFERRED |
| SUBMITTAL LIST ON DRAWING "COVER' PAGE. |
| |
| 8) PLEASE SHOW THE STAIR LANDING WIDTH AND DEPTH AT THE |
| TOP AND BOTTOM OF THE STAIR FBC 1011.6 STAIRWAY |
| LANDINGS. |
| THERE SHALL BE A FLOOR OR LANDING AT THE TOP AND BOTTOM |
| OF EACH STAIRWAY. THE WIDTH OF LANDINGS SHALL BE NOT |
| LESS THAN THE WIDTH OF STAIRWAYS SERVED. EVERY LANDING |
| SHALL HAVE A MINIMUM WIDTH MEASURED PERPENDICULAR TO |
| THE DIRECTION OF TRAVEL EQUAL TO THE WIDTH OF THE |
| STAIRWAY. WHERE THE STAIRWAY HAS A STRAIGHT RUN THE |
| DEPTH NEED NOT EXCEED 48 INCHES (1219 MM). |
| |
| 9) PLEASE SHOW THE PATIO FLOOR DECKING ATTACHMENTS FBC |
| WPB 107.2 |
| |
| 10) JOB VALUE SHOWN ON THE BUILDING PERMIT APPLICATION |
| APPEARS TO BE LOW - PLEASE PROVIDE A COST BREAK DOWN |
| (JOB VALUE IS MATERIAL AND LABOR) FBC 109.3 BUILDING |
| PERMIT VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| OFFICIAL, THE CLAIMED VALUATION |
| OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW |
| DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE |
| APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL |
| BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| ONLY LAND VALUE. |
| |
| |
| |