2022-06-15 10:36:05 | ROOFING PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: FLAT ROOF SHALL BE INSULATED PER NOTE ON ROOF |
| FRAMING PLAN PAGE 8/12 IN MASTER PERMIT 21091179. PLAN |
| PAGE UPLOADED TO THIS SUBMITTAL FOR YOUR REFERENCE. |
| |
| PLEASE REFERENCE NOA 20-0723.29 (MODIFIED BITUMEN) FOR |
| THE FOLLOWING COMMENTS: |
| |
| 1. STARTING ON PG. 10 OF THE NOA, THERE ARE ELEVEN |
| SYSTEMS FOR INSTALLATION OVER WOOD DECKS WITH |
| INSULATION TO CHOOSE FROM. DESIGNER SHALL SELECT SYSTEM |
| TO BE INSTALLED. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. LIMITATION #7, PAGE 48/48 OF NOA APPLIES TO ALL |
| ELEVEN INSULATED SYSTEMS. |
| PROVIDE INCREASED FASTENER DENSITIES FOR PERIMETER AND |
| CORNER AREAS DUE TO THE ENHANCED UPLIFT PRESSURES OF |
| THESE AREAS. |
| CALCULATIONS SHALL BE PREPARED, SIGNED AND SEALED BY A |
| FLORIDA REGISTERED DESIGN PROFESSIONAL. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |