Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-02-17 11:39:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) FOR CLARIFICATION AND COMFIRMATION, PLEASE PROVIDE
 THE APPROVED OCCUPANCY OF THIS BUILDING, IT IS AN
 EDUCATIONAL OR DAYCARE OCCUPANCY.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 1A) THERE IS AN INDICATION OF NEW CLASSROOMS WITH
 OPENINGS TO A COMMON INTERIOR AREA.
  
 THERE ARE NO DIMENSIONS INDICATED FOR THE OPENINGS.
  
 ARE DOORS PROPOSED FOR THESE OPENINGS?
  
 PLEASE PROVIDE DTAILS AND THE DIMENSIONS AND ENSURE
 THEY COMPLY WITH THE MINIMUM WIDTHS OF THE OCCUPANCY.
  
  
 2) THERE ARE NO INDICATIONS OF SMOKE ALARMS OR FIRE
 ALARM DEVICES WITHIN THE NEW CLASSROOMS.
  
 THIS OCCUPANCY WAS INSTALLED WITH A FIRE ALARM
 PREVIOUSLY.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT THAT FIRE
 ALARM/SA DEVICES WILL BE INSTALLED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  