Plan Review Notes For Permit 22020011 |
Permit Number |
22020011 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-17 11:39:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) FOR CLARIFICATION AND COMFIRMATION, PLEASE PROVIDE | | THE APPROVED OCCUPANCY OF THIS BUILDING, IT IS AN | | EDUCATIONAL OR DAYCARE OCCUPANCY. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | 1A) THERE IS AN INDICATION OF NEW CLASSROOMS WITH | | OPENINGS TO A COMMON INTERIOR AREA. | | | | THERE ARE NO DIMENSIONS INDICATED FOR THE OPENINGS. | | | | ARE DOORS PROPOSED FOR THESE OPENINGS? | | | | PLEASE PROVIDE DTAILS AND THE DIMENSIONS AND ENSURE | | THEY COMPLY WITH THE MINIMUM WIDTHS OF THE OCCUPANCY. | | | | | | 2) THERE ARE NO INDICATIONS OF SMOKE ALARMS OR FIRE | | ALARM DEVICES WITHIN THE NEW CLASSROOMS. | | | | THIS OCCUPANCY WAS INSTALLED WITH A FIRE ALARM | | PREVIOUSLY. | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT THAT FIRE | | ALARM/SA DEVICES WILL BE INSTALLED UNDER SEPARATE | | PERMIT AND SHOP DRAWINGS. | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|