| BUILDING REVIEW DENIED: |
| |
| THE PRIOR PLAN REVIEW COMMENTS HAVE NOT BEEN ANSWERED. |
| THE FOLLOWING ARE REQUIRED: |
| TEST REPORTS FOR AN UNDERLAYMENT THAT HAS BEEN TESTED |
| AND APPROVED FOR USE WITH VINYL FLOORING OVER A 6" |
| CONCRETE DECK WITH NO DROPPED CEILING. |
| |
| TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON THE |
| EXISTING SITE CONDITIONS. |
| TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: |
| E-84, E-90 & E-492. |
| ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| |
| FBC 603.1 FLAME SPREAD - ASTM E 84-09 |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| |
| |
| |
| |
| |