2022-03-03 13:09:15 | RESIDENTIAL (R3) REVISION SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| REVISION #22011190 |
| |
| 1- OK. |
| |
| ORIGINAL COMMENT: |
| 2- ATTIC BREEZE PRODUCT APPROVAL SUBMITTED STATES UNDER |
| LIMITS OF USE ON PAGE 4 OF 6 THAT "DESIGN OF SUPPORT |
| SYSTEM IS OUTSIDE THE SCOPE OF THIS REPORT". THIS |
| PRODUCT APPROVAL IS FOR A FAN TO BE MOUNTED ON A WOOD |
| OR STEEL & ALUMINUM CURB. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR THE CONSTRUCTION OF THE CURB SHOWING |
| COMPLIANCE WITH THE WIND DESIGN CRITERIA OF SEC. |
| R301.2.1 FBC-RESIDENTIAL. |
| NOTE: BUILDING SUBPERMIT MAY BE REQUIRED FOR FRAMING |
| INSPECTION. |
| |
| RESPONSE: |
| ROOF CURB INSTALLATION GUIDE SUBMITTED DOESN'T ADDRESS |
| THE WIND DESIGN CRITERIA. THE WIND DESIGN CRITERIA IS |
| REQUIRED. PROVIDE CURB ENGINEERING SHOWING COMPLIANCE |
| WITH THE WIND DESIGN CRITERIA. SEC. 107.2.1.2 CITY |
| AMENDMENTS. |
| NOTE: ENGINEER OF RECORD FOR ATTIC BREEZE FAN DOESN'T |
| INCLUDE THE CURB ASSEMBLY. SEE PRODUCT ASSEMBLY AS |
| EVALUATED INFORMATION ON PAGE 2 OF 6 OF PRODUCT |
| APPROVAL FL13339.4 R9 SUBMITTED. |
| |
| ORIGINAL COMMENT. |
| 3- THIS VENT IS ADDITIONAL WORK. PROVIDE THE VALUE FOR |
| ALL ADDITIONAL WORK. SEC. 109.3 CITY AMENDMENTS. |
| |
| RESPONSE: |
| NOT ADDRESSED. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |