2022-02-08 17:38:37 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| REVISION #22011190 |
| |
| NOTE: |
| LEVEL 2 ALTERATION. SEC. 603 FBC-EXISTING BUILDING. |
| SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION |
| ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- THIS IS A TOWNHOUSE. ROOF DIAGRAM SUBMITTED SHOWS |
| THE SOLAR ATTIC FAN TO BE LOCATED LESS THAN FOUR FEET |
| OF THE FIRE RATED DEMISING WALL. NO OPENING ALLOWED IN |
| THIS AREA. REVISE AS REQUIRED. CLEARLY SPECIFY DISTANCE |
| FROM FIRE RATED DEMISING WALL. SEC. R302.2 |
| FBC-RESIDENTIAL. |
| |
| 2- ATTIC BREEZE PRODUCT APPROVAL SUBMITTED STATES UNDER |
| LIMITS OF USE ON PAGE 4 OF 6 THAT "DESIGN OF SUPPORT |
| SYSTEM IS OUTSIDE THE SCOPE OF THIS REPORT". THIS |
| PRODUCT APPROVAL IS FOR A FAN TO BE MOUNTED ON A WOOD |
| OR STEEL & ALUMINUM CURB. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR THE CONSTRUCTION OF THE CURB SHOWING |
| COMPLIANCE WITH THE WIND DESIGN CRITERIA OF SEC. |
| R301.2.1 FBC-RESIDENTIAL. |
| NOTE: BUILDING SUBPERMIT MAY BE REQUIRED FOR FRAMING |
| INSPECTION. |
| |
| 3- THIS VENT IS ADDITIONAL WORK. PROVIDE THE VALUE FOR |
| ALL ADDITIONAL WORK. SEC. 109.3 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE |
| REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |