Plan Review Notes
Plan Review Notes For Permit 22011186
Permit Number 22011186
Review Stop B
Sequence Number 2
Notes
Date Text
2022-12-02 19:09:20NEW DUPLEX (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY.
  
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
 1- OK.
  
 ORIGINAL COMMENT:
 2-SINGLE HUNG BEDROOM EGRESS WINDOWS SIZE (3'-1' X
 4'-10-1/2") DOESN'T SEEM TO COMPLY WITH THE MINIMUM
 CLEAR HEIGHT OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. TYPICALLY, SINGLE HUNG WINDOWS WITH A
 63 INCHES HEIGHT ARE THE ONES THAT COMPLY WITH THIS
 REQUIREMENT. REVISE AS REQUIRED OR PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING COMPLIANCE ALL
 THE EGRESS REQUIREMENTS.
  
 RESPONSE:
 PARTIALLY ADDRESSED. (DISCUSSED WITH ROBERT BROWN,
 BUILDING OFFICIAL). SINCE THIS IS NEW CONSTRUCTION AND
 THE SPECIFIED WINDOW SIZE IS SMALLER THAN TYPICAL
 EGRESS SIZE AND THE ARCHITECT'S SPECIFIED WINDOW IS
 BASED ON SPECIFIC MANUFACTURER AND SPECIFIC SIZE WITH
 AN ADDITIONAL CONDITION TO MEET THE EGRESS
 REQUIREMENTS, THEN BUILDING OFFICIAL REQUIRES ARCHITECT
 OF RECORD TO SPECIFY ON PLANS HOW THE SPECIFIED WINDOW
 MEETS THE EGRESS REQUIREMENT. THIS IS REQUIRED IN ORDER
 FOR INSPECTOR TO VERIFY THIS CONDITION IN THE FIELD.
 ALSO, PLEASE UPLOAD THE MANUFACTURE'S CUT SHEETS ON A
 SEPARATE FILE NOT WITH THE RESPONSE LETTER. RESPONSE
 LETTER IS ONLY TO HELP EXPEDITE THE REVIEW PROCESS AND
 WILL NOT BE PART OF THE PERMIT PACKAGE. THE WINDOW CUT
 SHEETS ARE PART OF THE PERMIT PACKAGE. ALSO, SAME THING
 APPLIES TO THE ICYNENE ICC EVALUATION REPORT.
  
 ORIGINAL COMMENT:
 3- ARCHITECT TO CLEARLY SPECIFY ALL ROOF LIVE AND DEAD
 LOADS. CLEARLY SPECIFY TRUSS TOP CHORD LIVE AND DEAD
 LOADS AND BOTTOM CHORD LIVE AND DEAD LOADS. NOTE:
 INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 RESPONSE:
 ROOF BOTTOM CHORD LIVE LOAD DOESN'T COMPLY WITH TABLE
 R301.5 FBC-RESIDENTIAL. MIN. BOTTOM CHORD LIVE LOAD IS
 10PSF. REVISE INFORMATION AS REQUIRED.
  
 ORIGINAL COMMENT:
 4- PROVIDE DRAINAGE PLAN SHOWING EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES. PROVIDE SURVEY SHOWING GRADE
 ELEVATIONS AND PROPOSED BUILDING.
 SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DETAIL 1 ON SHEET A.0.1 DOESN'T REFLECT SITE
 DRAINAGE PLAN. ALSO, PROVIDE DETAIL SHOWING HOW RAISING
 THE GRADE 6 INCHES AT THE PROPERTY LINE. IF RETAINING
 WLL REQUIRED, THEN NEED TO PROVIDE COMPLETE RETAINING
 WALL DETAILS/SPECS UNDER A SEPARATE PERMIT.
  
 RESPONSE:
 DRAINAGE PLAN DOESN'T SHOW EXISTING AND PROPOSED
 ELEVATIONS. SURVEY SHOWING THE ELEVATIONS WAS NOT
 PROVIDED. INFORMATION ON DETAIL 1 ON SHEET A-0.1
 DOESN'T SHOW HOW RAISING THE GRADE 6 INCHES AT THE
 PROPERTY LINE. IF RETAINING WILL BE REQUIRED, THEN NEED
 TO PROVIDE COMPLETE RETAINING WALL DETAILS/SPECS UNDER
 A SEPARATE PERMIT.
 ALSO, PROVIDE SWALE DETAIL/SECTION FOR BOTH SIDES (EAST
 AND WEST) OF PROPOSED STRUCTURE.
  
 5- WALL SEPARATING THE TWO UNITS.
  
 ORIGINAL COMMENT:
 A)PROVIDE COMPLETE WALL SECTION DETAIL AND
 SPECIFICATIONS FOR ONE HOUR FIRE RESISTANCE RATING
 SHOWING COMPLIANCE WITH SEC. R302.3 FBC-RESIDENTIAL.
 SHOW COMPLIANCE WITH ASTM E119, UL 263 OR SEC. 703.3
 FBC-BUILDING.
  
 RESPONSE:
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR TYPE OF
 "MUD" TO BE USED TO SEAL ALL OPENINGS AND PENETRATIONS
 AS SPECIFIED ON DETAIL 2 ON SHEET A.4.
 (SEC. 107.2.1 CITY AMENDMENTS. SEC. 703.3
 FBC-BUILDING).
  
 ALSO, DETAIL 2 ON SHEET A.4 STATES THAT MASONRY WALL
 BETWEEN UNIT 1 AND UNIT 2 IS A 2 HR WALL. NEED TO
 SPECIFY THE SPECIFIC TYPE OF CONCRETE BLOCK TO BE
 CONSIDERED 2 HOUR. SEE UL ASSEMBLY U905 FOR SPECIFIC
 TYPE AND REVISE AS REQUIRED. PROVIDE COMPLETE DETAIL
 ASSEMBLY.
  
 ORIGINAL COMMENT:
 B)PROVIDE DETAILS/SPECS FOR WALL THROUGH PENETRATIONS.
 SEC. R302.4.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 DETAILS PROVIDED ON SHEET A.4 ARE FOR GYPSUM WALLS.
 THIS IS MASONRY CONSTRUCTION.
 NOTE: PROVIDE DETAIL/SPECIFICATIONS FOR RECEPTACLES AND
 ANY OTHER PENETRATIONS ON THE FIRE RATED DEMISING WALL.
  
 ORIGINAL COMMENT:
 6- THERE ARE TWO DIFFERENT SPECIFICATIONS FOR ROOF
 SHEATHING ON SHEET S.2. ROOF FRAMING NOTE #1 AND
 INFORMATION SHOWN ON TABLE R803.2.3.1 FOR SHEATHING
 ATTACHMENT BELOW DON'T MATCH. REVISE AS REQUIRED TO
 MATCH TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 ROOF FRAMING NOTES SPECIFY 10D NAILS. CLEARLY SPECIFY
 TYPE OF NAILS. SEC. R803.2.3.1 FBC-RESIDENTIAL REQUIRES
 RING SHANK NAILS. SPECIFY THIS ON PLANS.
  
 ORIGINAL COMMENT:
 7- DESIGN PRESSURES FOR WINDOW #2 ON NORTH AND SOUTH
 ELEVATIONS ARE TOO LOW. THESE WINDOWS ARE LOCATED IN
 THE END ZONE. REVISE AS REQUIRED. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DESIGN PRESSURES WERE LOWERED INSTEAD OF BEING
 INCREASED. REVISE AS REQUIRED OR PROVIDE CALCULATIONS
 FOR EACH OPENING.
  
 ORIGINAL COMMENT:
 8- GABLE END DETAIL ON SHEET ON SHEET S.2: NEED TO
 SPECIFY TWO WATER RESISTIVE BARRIERS WHEN STUCCO IS
 APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 RESPONSE LETTER SAYS "(2) WATER RESISTIVE BARRIERS ARE
 SPECIFIED. SEE REVISED SECTION NOTE #3 ON SHEET A.4".
 THIS INFORMATION WAS NOT PROVIDED.
  
 ORIGINAL COMMENT:
 9- WIND RESISTANCE OF EXTERIOR SOFFITS: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOFFIT
 CONSTRUCTION SHOWING COMPLIANCE WITH SEC. R704
 FBC-RESIDENTIAL.
  
 RESPONSE:
 RESPONSE LETTER SAYS "SOFFITS ARE STUCCO. SEE NOTE #2
 ON SHEET A.4".
 THIS INFORMATION WAS NOT PROVIDED.
 NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY TYPE OF METAL
 PLASTER BASE FOR CEILINGS SHOWING COMPLIANCE WITH TABLE
 3 OF ASTM C1063.
  
 10- OK.
 11- OK.
 12- OK.
  
 ORIGINAL COMMENT:
 13-PROVIDE DOOR AND WINDOW DOOR STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DETAILS ON SHEET A.4.1 DON'T SPECIFY FASTENING OF THE
 BUCKS. DESIGNER OF RECORD NEEDS TO SPECIFY FASTENER
 TYPE AND SIZE/SPACING. CITING PER CODE SECTION IS NOT
 ALLOWED. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- OK.
  
 ORIGINAL COMMENT:
 15- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 RESPONSE LETTER SAYS "THIS HAS BEEN ADDED AS A DEFERRED
 SUBMITTAL ON REVISED SHEET A.0". REVISED SHEET DOESN'T
 SHOW THIS. ALSO, THE ICC EVALUATION REPORT WAS UPLOADED
 IN PROJECTDOX IN THE SAME FILE WITH THE RESPONSE
 LETTER. PLEASE UPLOAD THE ICC EVALUATION REPORT
 REVIEWED/APPROVED BY THE ARCHITECT ON A SEPARATE FILE
 NOT WITH THE RESPONSE LETTER.
  
 16-DEFERRED SUBMITTAL. PRODUCT APPROVALS (FAC
 61G20-3.001):
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 18- REVISE ENERGY CALCULATIONS:
  
 RESPONSE:
 ENERGY CALCULATIONS WERE NOT REVISED. SAME ITEMS APPLY.
 SEE BELOW:
  
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B)ITEM #2 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 C)ITEM #3 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 D)CEILING R-VALUE INFORMATION ON PAGE 1 DOESN'T MATCH
 INFORMATION ON PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)WATER HEATER IS ELECTRIC NOT GAS. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F) ROOF TYPE AND MATERIAL SPECIFIED ON SECOND PAGE IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  