2022-09-27 18:59:59NEW DUPLEX (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22011186
 910 4TH ST
  
 1- ALL PLANS NEED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OF RECORD WHEN SUBMITTING FOR PUBLIC RECORDS.
 SEC. 481 F.S.
  
 2-SINGLE HUNG BEDROOM EGRESS WINDOWS SIZE (3'-1' X
 4'-10-1/2") DOESN'T SEEM TO COMPLY WITH THE MINIMUM
 CLEAR HEIGHT OPENING REQUIREMENTS OF SEC. R310.2.1
 FBC-RESIDENTIAL. TYPICALLY, SINGLE HUNG WINDOWS WITH A
 63 INCHES HEIGHT ARE THE ONES THAT COMPLY WITH THIS
 REQUIREMENT. REVISE AS REQUIRED OR PROVIDE
 MANUFACTURER'S SPECIFICATIONS SHOWING COMPLIANCE ALL
 THE EGRESS REQUIREMENTS.
  
 3- ARCHITECT TO CLEARLY SPECIFY ALL ROOF LIVE AND DEAD
 LOADS. CLEARLY SPECIFY TRUSS TOP CHORD LIVE AND DEAD
 LOADS AND BOTTOM CHORD LIVE AND DEAD LOADS. NOTE:
 INCLUDE THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
  
 4- PROVIDE DRAINAGE PLAN SHOWING EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES. PROVIDE SURVEY SHOWING GRADE
 ELEVATIONS AND PROPOSED BUILDING.
 SEC. R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DETAIL 1 ON SHEET A.0.1 DOESN'T REFLECT SITE
 DRAINAGE PLAN. ALSO, PROVIDE DETAIL SHOWING HOW RAISING
 THE GRADE 6 INCHES AT T HE PROPERTY LINE. IF RETAINING
 WALL REQUIRED, THEN NEED TO PROVIDE COMPLETE RETAINING
 WALL DETAILS/SPECS UNDER A SEPARATE PERMIT.
  
 5- WALL SEPARATING THE TWO UNITS.
 A)PROVIDE COMPLETE WALL SECTION DETAIL AND
 SPECIFICATIONS FOR ONE HOUR FIRE RESISTANCE RATING
 SHOWING COMPLIANCE WITH SEC. R302.3 FBC-RESIDENTIAL.
 SHOW COMPLIANCE WITH ASTM E119, UL 263 OR SEC. 703.3
 FBC-BUILDING.
 NOTE: CLARIFY IF DETAIL 2 ON SHEET A.4 IS TO SHOW
 COMPLIANCE WITH EXCEPTION #2. IF THIS IS THE INTENTION,
 THEN NEED TO REVISE DETAIL TO SPECIFY THE REQUIRED TYPE
 OF FIRE RATED CEILING.
  
 B)PROVIDE DETAILS/SPECS FOR WALL THROUGH PENETRATIONS.
 SEC. R302.4.1 FBC-RESIDENTIAL.
  
 6- THERE ARE TWO DIFFERENT SPECIFICATIONS FOR ROOF
 SHEATHING ON SHEET S.2. ROOF FRAMING NOTE #1 AND
 INFORMATION SHOWN ON TABLE R803.2.3.1 FOR SHEATHING
 ATTACHMENT BELOW DON'T MATCH. REVISE AS REQUIRED TO
 MATCH TO AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 7- DESIGN PRESSURES FOR WINDOW #2 ON NORTH AND SOUTH
 ELEVATIONS ARE TOO LOW. THESE WINDOWS ARE LOCATED IN
 THE END ZONE. REVISE AS REQUIRED. SEC. R301.2.1
 FBC-RESIDENTIAL.
 NOTE: CLARIFY WHY THE DESIGN PRESSURES FOR WINDOW #3
 ARE DIFFERENT ON THE EAST AND WEST ELEVATIONS IF THEY
 ARE THE SAME SIZE AND ARE LOCATED IN THE SAME ZONE?
  
 8- GABLE END DETAIL ON SHEET ON SHEET S.2: NEED TO
 SPECIFY TWO WATER RESISTIVE BARRIERS WHEN STUCCO IS
 APPLIED TO WOOD AS REQUIRED BY SEC. R703.7.3
 FBC-RESIDENTIAL.
  
 9- WIND RESISTANCE OF EXTERIOR SOFFITS: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOFFIT
 CONSTRUCTION SHOWING COMPLIANCE WITH SEC. R704
 FBC-RESIDENTIAL.
  
 10- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 WALL FLASHING AT ALL EXTERIOR OPENINGS.. SEC. R703.4
 FBC-RESIDENTIAL.
  
 11-FOUNDATION PLAN SHEET S.1:
 A)FOOTING DIMENSIONS AND REINFORCING SPECIFICATIONS FOR
 MF-24 SPECIFIED ON THE FOOTING SCHEDULE ARE INCORRECT.
 REVISE AS REQUIRED. SEC. R401.2 FBC-RESIDENTIAL.
  
 B)PROVIDE SPECIFICATIONS FOR FOOTING AT ENTRY PORCH
 COLUMNS. SEC. R401.2 FBC-RESIDENTIAL.
 NOTE: COORDINATE DETAIL 9/S.3 WITH FOOTINGS SHOWN ON
 THE FOUNDATION PLAN.
  
 12-ROOF FRAMING PLAN SHEET S.2: PROVIDE
 DETAIL/SPECIFICATIONS FOR CONNECTION OF ENTRY PORCH
 COLUMNS TO WOOD BEAM. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 13-PROVIDE DOOR AND WINDOW DOOR STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 14- PROVIDE DETAILS AND SPECIFICATIONS FOR DECORATIVE
 SHUTTERS INSTALLATION. SPECIFY FASTENING. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 15- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE R-30 INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 16-PRODUCT APPROVALS
 PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC 61G20-3.001
 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY WOOD DOOR AS SPECIFIED ON PLANS.
 B)WOOD FRENCH DOOR AS SPECIFIED ON PLANS.
 C)SINGLE HUNG WINDOWS.
 D)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 E)HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 E)SHINGLES.
 F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 18- REVISE ENERGY CALCULATIONS:
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME, BUILDER NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B)ITEM #2 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 C)ITEM #3 ON PAGE 1 IS INCORRECT. THIS IS A MULTIFAMILY
 BUILDING. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 D)CEILING R-VALUE INFORMATION ON PAGE 1 DOESN'T MATCH
 INFORMATION ON PLANS.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 E)WATER HEATER IS ELECTRIC NOT GAS. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 F) ROOF TYPE AND MATERIAL SPECIFIED ON SECOND PAGE IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN
 PROFESSIONAL FEES. VALUATION WAS UPDATED TO $288,952.
 OWES $367.14.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  