2022-02-07 15:43:01 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-22011175 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PERMIT APPLICATION HAS A VALUE OF 1,200.00 BUT | | THE CONTRACT SUBMITTED HAS A VALUE OF 12,000.00 PLEASE | | ADJUST THE VALUE ON THE PERMIT APPLICATION. | | | | 2) THE FIRST FLOOR DRAWING SHOWS A RETURN IN THE | | GARAGE, REMOVE THIS RETURN FROM THE GARAGE. FBC RES | | M1602.2-4 | | | | 3) PLEASE SHOW HOW THE RETURN AIR WILL FLOW FROM THE | | 2ND FLOOR TO THE RETURN ON THE 1ST FLOOR. FBC RES | | M1602.3 | | | | 4) SHOW THE RETURN AIR PATH FROM THE 2ND FLOOR OFFICE | | TO THE AHU RETURN. FBC RES M1602.3 | | | | 5) WHAT IS THE DUCT SIZE THAT SUPPLIES THE AIR TO THE | | 2ND STORY? | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|