2022-02-02 13:39:021ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22011170
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THE BATH EXHAUST DUCT AND TERMINATION
 LOCATION. FBC 107.2.1
  
 2) PLEASE SHOW THE DRYER DUCT AND TERMINATION LOCATION.
 FBC RES M1502
  
 3) IS THERE GOING TO BE A HOOD INSTALLED ABOVE THE
 RANGE? IF SO, IS IT TO BE DUCTED TO THE EXTERIOR? IF
 SO, PLEASE PROVIDE THE CFM?S OF THE EXHAUST FAN FOR THE
 HOOD AND SHOW MAKE UP AIR IF REQUIRED. FBC RES M1503.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  